Faults may be reset with the Reset radio button.
Figure 5.19 Reset fault com m and
Suspended Time Remaining
The Suspended Time Remaining box is not configurable. It is the time remaining when energy savings mode is suspended. It
is activated when energy saving mode has been active and inactive too much times and the system will suspend its activation
for a period.
Module Redundancy Status
Module redundancy is usually chosen during system setup. Redundancy may be enabled only with Administrator or Service
permissions. Proper operation requires the presence of at least a second module, but the system may encompass more
modules.
To enable module redundancy:
1. Log in with Administrator or Setup permissions.
2. Touch the SETUP tab.
3. Touch the Context Menu icon and select UPS Settings.
4. In the Module Redundancy drop-down menu, touch Enable.
5. Touch the Save button to save the new setting or touch Cancel to exit without saving.