Document: LT0344 Vigilant MX1 Operator Manual
Issue 2.4 8 August 2017 Page 3-7
Refer to Disabling or Enabling a range of Points (page 6-7).
ALRM DEVF3 allows the Alarm Devices to be enabled/disabled.
ANCILSF4 allows the ancillary groups to be enabled/disabled (see
page 3-7).
This function requires Access Level 2.
From the Disable Menu press ALRM DEVF3 to enable/disable the
alarm devices. The confirmation screen will show the action that is about
to be performed (i.e., enable or disable) and request the OK key be
pressed.
If OK is pressed the action is carried out, otherwise press CANCEL to
return to the previous screen.
This function is the same as the Internal Silence Alarms function see
below.
This function requires Access Level 2.
To activate the internal Silence Alarms function, press the
SILENCE/RESOUND ALARMS key.
The yellow ALARM DEVICES DISABLED indicator will light and the
alarm devices will be switched off, if they were on.
This function requires Access Level 2.
To cancel the internal Silence Alarms function, press the
SILENCE/RESOUND ALARMS key again. The MX1 will ask for
confirmation of this action if the alarm devices will then turn on.
Press OK to confirm.
The yellow ALARM DEVICES DISABLED indicator will go out, as well
as the DISABLES indicator if there are no other disables present.
This function requires Access Level 2.
Many MX1 installations have functionality for control of lifts, air-
conditioning systems and so forth during alarm conditions. When the
panel is undergoing tests it may be necessary to disable this functionality
in order to avoid disruption to site occupants.
Alarm