Vigilant MX1 Operator Manual Document: LT0344
Page 6-12 8 August 2017 Issue 2.4
Zones 1 to 3 | ALL
F1 enables all in range |
F4 enables normal in range |
| NORMAL
Fig 6-19 – Choice for Enabling a Range Of Zones
Selecting ALLF1 will enable all zones in the range, irrespective of their
status.
If any of these zones are in Alarm or Fault states, they will
resume their programmed behaviour in activating alarm
devices and fault outputs once they have been enabled.
If NORMALF4 is selected, only those zones in the range that are in the
normal state will be enabled. Since (dependant on the configuration in
use) enabling zones in alarm could activate remote signalling, alarm
devices, etc., this option permits the system to be returned to service
without accidentally enabling an alarm and perhaps signalling the
brigade.
In the confirmation display press OK to enable the zones in the range, or
CANCEL to abort the command.
Attempting to enable a zone that has all of its points
disabled will not work even though it falls within the
specified range of zones. To enable the zone, one or
more of its points will need to be enabled first.
This function requires Access Level 2.
From the recall zone status display, press MENU or MENUF4 to display
the menu options, then press TESTF3 to display the zone test menu.
Alternatively, from the base display press TESTS, INITIATEF4,
ZONEF1 and enter the zone number.
Zone 001 Std Detection G1 |ALRM TST
Office | OPERATE
Normal |AUTO RST
| FLT TST
Fig 6-20 – Zone Test Status and Menu