Vigilant MX1 Operator Manual Document: LT0344
Page 4-4 8 August 2017 Issue 2.4
The <zone text> is the descriptive text for the zone.
The <event text> is one of the following:
This zone has become Active (distinct from Alarm
state). Output points mapped to the zone become
operated.
One or more of the detectors in this zone has gone into
Alarm.
The alarm on this zone has been acknowledged by a
user.
The alarm on this zone has cleared.
A test of the processing of alarm conditions in this zone
has been started.
This zone has been automatically disabled/ isolated, for
example following operation and restoration of the NZ
Silence Alarms keyswitch.
Auto-Reset mode has been started for this zone.
Auto-Reset mode for this zone has been cancelled due
to a timeout period with no new alarms.
The event code wasn’t recognised by this panel.
This zone has stopped being Active.
All output devices in this zone have been switched out
of the operated condition.
This zone has been disabled/enabled by an operator
command respectively.
One or more of the devices in this zone is faulty.
All faults on this zone have cleared.
A test of the processing of fault conditions in this zone
has been started.
A fault test has been terminated by an operator.
A detector mapped to this zone has signalled alarm,
but the zone alarm is not signalled yet because the
alarm is being investigated (AAF alarm) or a second
point in alarm is required (the zone is programmed for
dual-hit operation).
Input activated
Input
deactivated
An input point mapped to this zone has become Active
(distinct from Alarm) or has stopped being Active,
respectively.
This zone has returned to normal.
One or more non-disabled output devices in this zone
have been switched into the operated condition.
An Operate Test command has been issued for this
zone. This will result in all the zone’s output points
being test-operated.
One or more of the detectors in this zone is in a pre-
alarm condition.
The pre-alarm condition on this zone has cleared.
This zone has been reset by an operator command.
The current test on this zone has been cancelled.
The current test on this zone has failed.
The current test on this zone has passed.