Mobile Generator
General Maintenance
Continued from the previous page.
2. Remove the filter equalizing element (b).
3. Use the disposable filter tool (c) to aid in removing the filter element (d). Use the
appropriate end of the tool, depending on the color of the plastic on the filter.
Note: The disposable filter tool will make a “click” sound. This indicates that the
filter element is properly engaged.
4. Clean the filter cap and threads with warm water and a clean cloth.
Note: Inspect the filter cap for cracks or leaks. If the threads are damaged, replace
the filter cap.
Installation
1. Insert the equalizing element into the new filter.
2. Insert the filter assembly into the aftertreatment dosing unit.
3. Re-install the filter cap and torque it to 20 Nm (14.8 ft.lbs.).
Result
The aftertreatment DEF dosing unit filter has now been replaced.