7.3 Genset Pre-Alarms and Alarms (Shut-Down Conditions)
Background
The genset controller monitors variables of engine and machine function. The
genset controller is programmed to signal pre-alarm conditions, and to shut down
the machine when an alarm condition exists.
Pre-alarms
Pre-alarm conditions are:
■ Low fuel level
■ High coolant temperature
■ Low oil pressure
■ Time to maintenance
During a pre-alarm condition, the LCD panel (a) displays the type of pre-alarm, and
the LED (b) flashes. The machine is not shut down.
Alarms/
shutdowns
Shut-down conditions are:
■ Low fuel level
■ High coolant temperature
■ Low oil pressure
■ Overspeed/Underspeed
■ Overcrank
■ Low coolant level (if equipped)
■ Overcurrent
During an alarm condition, the LCD panel (a) displays the type of alarm, the LED
(b) illuminates continuously, and the machine is shut down.
A
Ø
HZ
V
DIAGNOSTICS
DIAGNOSEN
DIAGNOSTICOS
DIAGNOSTICS
R
Basler
AUSAUS
APAGADOAPAGADO
ARRETARRET
OFFOFF
REMOTE STARTREMOTE START
FERNSTARTFERNSTART
ARRANQUE REMOTOARRANQUE REMOTO
DEMARRAGE A DEMARRAGE A
DISTANCEDISTANCE
START / LAUFENSTART / LAUFEN
ARRANQUE / MARCHAARRANQUE / MARCHA
DEMARRER / MARCHEDEMARRER / MARCHE
START / RUNSTART / RUN
E
M
E
R
G
E
N
C
Y
S
T
O
P
A
Ø
HZ
V
R
Basler
DIAGNOSTICS
DIAGNOSEN
DIAGNOSTICOS
DIAGNOSTICS
042563
wc_gr010359
b
a
Variable Normal Pre-Alarm Alarm To Reset
Fuel level >15% 15% 5% Fill fuel tank. Toggle start switch.
Coolant temp 85°C±8 105°C 115°C Add coolant. Toggle start switch.
Oil pressure 60–80 psi 20 psi 15 psi Add engine oil. Toggle start switch.
Overspeed 60 Hz — 66 Hz Toggle start switch.
Underspeed 60 Hz — 54 Hz Toggle start switch.
Overcrank — — After 3 attempts Toggle start switch.
Time to maintain 250 hours 0 hours — Reset genset controller.
Coolant level Above sender — Below sender Add coolant. Toggle start switch.