Mobile Generator Working with Basler Controller
At the
PASSWORD
prompt
To log in when prompted to enter the password, do the following:
1. The password entry screen appears with a letter “A” as the default character.
Use the up/down arrow buttons to change the “A” to “O”. Then, press the right
arrow button to move the cursor to the next position.
2. Use the up/down arrow buttons to select “P”. Then, press the check mark
button.
3. A screen for the parameter, similar to that shown below left (A), will appear. The
word “~~EDIT~~” will be displayed. Whenever “~~EDIT~~” is displayed, it
means that you are able to change the parameter. Use the up/down arrow
buttons to change the setting. Then, press the check mark button to accept the
new value.
Note: If the genset controller displays the screen (B), it means that the parameter
cannot be changed by the operator. Do not re-enter the password even though you
are requested to do so; instead, press the “X” button to cancel the operation and
return to the previous screen. If you do re-enter the password (by pressing the
check mark button), you will be logged out. In such cases, turn the machine off,
then back on again, and restart the procedure from the beginning.