Watlow EZ-ZONE
®
PMI Controller 120 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
r.En
r.En
Control Loop (1)
Remote Set Point
Set whether this
loop will use a re-
mote set point.
no No (59)
yEs Yes (106)
No
Instance 1
Map 1 Map 2
2200 2680
0x6B
(107)
1 to 2
0x15
(21)
48 7021 uint
RWES
r.ty
r.ty
Control Loop (1)
Remote Set Point
Type
Set what type of
set point will be
used.
aUto Auto (10)
ЛЏan Manual (54)
Auto Instance 1
Map 1 Map 2
2202 2682
0x6B
(107)
1 to 2
0x16
(22)
- - - - 7022 uint
RWES
SFn.b
SFn.b
Control Loop (1)
Source Function B
Set the source for
the Remote Set
Point.
Note:
Applies to models
with the 8th digit
of the part number
= 7
nonE None (61)
d.bi Digital Bus In-
put (1993)
Instance 1
Map 1 Map 2
2204 2684
Instance 2
Map 1 Map 2
2284 2764
0x6B
(107)
1 to 2
0x17
(23)
- - - - 7023 uint
RWES
Si.b
Si.b
Control Loop (1)
Source Instance B
Set the instance
of the function se-
lected above.
Note:
Applies to models
with the 8th digit
of the part number
= 7
1 to 6 Instance 1
Map 1 Map 2
2206 3562
Instance 2
Map 1 Map 2
2286 3632
0x6B
(107)
1 to 2
0x18
(24)
- - - - 7024 un-
signed
8-bits
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set

Table of Contents