Watlow EZ-ZONE
®
PMI Controller 121 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
Ufa
UFA
Control Loop (1 to
2)
Auto-to-Manual
Power
Select what the
controller out-
puts will do when
the user switches
control to manual
mode.
off Off, sets output
power to 0% (62)
bpLs Bumpless
transfer, maintains
same output power,
if it was less than 75%
and stable, otherwise
0% (14)
ЛЏan Fixed Power,
sets output power to
Fixed Power setting
(54)
UsEr User, sets
output power to last
open-loop set point
the user entered
(100)
User Instance 1
Map 1 Map 2
2182 2662
Instance 2
Map 1 Map 2
2262 2742
0x6B
(107)
1 to 2
0xC (12)
- - - - 7012 uint
RWES
faiL
FAiL
Control Loop (1 to
2)
Input Error Power
Select what the
controller outputs
will do when an in-
put error switches
control to manual
mode.
off Off, sets output
power to 0% (62)
bpLs Bumpless
transfer, maintains
same output power,
if it was less than 75%
and stable, otherwise
0% (14)
ЛЏan Fixed Power,
sets output power to
Fixed Power setting
(54)
UsEr User, sets
output power to last
open-loop set point
the user entered
(100)
User Instance 1
Map 1 Map 2
2184 2664
Instance 2
Map 1 Map 2
2264 2744
0x6B
(107)
1 to 2
0xD (13)
- - - - 7013 uint
RWES
ЛЏan
MAn
Control Loop (1 to
2)
Fixed Power
Set the manual
output power level
that will take ef-
fect if an input er-
ror failure occurs
while User Failure
Action is set to
Fixed Power.
Set Point Open Loop
Limit Low to Set
Point Open Loop Lim-
it High (Setup Page)
0.0 Instance 1
Map 1 Map 2
2180 2660
Instance 2
Map 1 Map 2
2260 2740
0x6B
(107)
1 to 2
0xB (11)
- - - - 7011 float
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set