Watlow EZ-ZONE
®
PMI Controller 124 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
id.s
id.S
Control Loop (1 to
2)
Idle Set Point *
Set a closed loop
set point that can
be triggered by an
event state.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
75.0°F
or units
24.0°C
Instance 1
Map 1 Map 2
2176 2656
Instance 2
Map 1 Map 2
2197 2736
0x6B
(107)
1 to 2
9
50 7009 float
RWES
sp.Lo
SP.Lo
Control Loop (1 to
2)
Minimum Manual
Power
Set the minimum
value of the open-
loop set point
range.
-100.0 to 100.0% -100 Instance 1
Map 1 Map 2
2168 2648
Instance 2
Map 1 Map 2
2248 2728
0x6B
(107)
1 to 2
5
54 7005 float
RWES
sp.hi
SP.hi
Control Loop (1 to
2)
Maximum Manual
Power
Set the maximum
value of the open-
loop set point
range.
-100.0 to 100.0% 100 Instance 1
Map 1 Map 2
2170 2650
Instance 2
Map 1 Map 2
2250 2730
0x6B
(107)
1 to 2
6
55 7006 float
RWES
o.sp
o.SP
Control Loop (1 to
2)
Manual Power *
Set a fixed level
of output power
when in manual
(open-loop) mode.
-100.0 to 100.0%
(heat and cool) 0 to
100.0% (heat only)
-100.0 to 0% (cool
only)
0.0 Instance 1
Map 1 Map 2
2162 2642
Instance 2
Map 1 Map 2
2242 2722
0x6B
(107)
1 to 2
2
51 7002 float
RWES
C.ЛЏ
C.M
Control Loop (1 to
2)
Control Mode *
Select the method
that this loop will
use to control.
off Off (62)
aUto Auto (10)
ЛЏan Manual (54)
Auto Instance 1
Map 1 Map 2
1880 2360
Instance 2
Map 1 Map 2
1950 2430
0x97
(151)
1 to 2
1
63 8001 uint
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set