Watlow EZ-ZONE
®
PMI Controller • 126 • Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
o.tb
o.tb
Output Digital (1
to 4)
Fixed Time Base
Set the time base
for fixed-time-base
control.
0.1 to 60.0 seconds
(solid-state relay or
switched dc)
5.0 to 60.0 seconds
(mechanical relay
or NO-ARC power
control)
1.0 sec.
for SSR
or swdc
5.0 for
relay
Instance 1
Map 1 Map 2
884 1004
Offset to
next in-
stance (Map
1 & Map 2)
equals +30
0x6A
(106)
1 to 4
3
86 6003 float
RWES
o.Lo
o.Lo
Output Digital (1
to 4)
Low Power Scale
The power output
will never be less
than the value
specified and will
represent the value
at which output
scaling begins.
0.0 to 100.0% 0.0% Instance 1
Map 1 Map 2
896 1016
Offset to
next in-
stance (Map
1 & Map 2)
equals +30
0x6A
(106)
1 to 4
9
87 6009 float
RWES
o.hi
o.hi
Output Digital (1
to 4)
High Power Scale
The power output
will never be great-
er than the value
specified and will
represent the value
at which output
scaling stops.
0.0 to 100.0% 100.0% Instance 1
Map 1 Map 2
898 1018
Offset to
next in-
stance (Map
1 & Map 2)
equals +30
0x6A
(106)
1 to 4
0x0A
(10)
88 6010 float
RWES
o.ty
o.ty
Output Process (1
or 3)
Type
Select whether the
process output will
operate in volts or
milliamps.
uoLt Volts (104)
ЛЏA Milliamps (112)
Volts Instance 1
Map 1 Map 2
720 840
Instance 3
Map 1 Map 2
800 920
0x76
(118)
1 or 3
1
95 18001 uint
RWES
Fn
Fn
Output Process (1
or 3)
Function
Set the type of
function that will
drive this output.
oFF Off (62)
hEat Heat (36)
CooL Cool (20)
dUpL Duplex (212)
ALЛЏ Alarm (6)
Ent.A Profile Event
Out A (233)
Ent.b Profile Event
Out B (234)
rЛЏt Retransmit
(213)
Off Instance 1
Map 1 Map 2
722 842
Instance 3
Map 1 Map 2
802 922
0x76
(118)
1 or 3
2
96 18002 uint
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set