Watlow EZ-ZONE
®
PMI Controller • 127 • Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
r.Sr
r.Sr
Output Process (1
or 3)
Retransmit Source
Select the value
that will be retrans-
mitted.
Ai Analog Input
(142)
StPt Set Point (85)
CUrr Current Sam-
ple and hold (22)
Pu Process Value
(241)
Analog
Input
Instance 1
Map 1 Map 2
724 844
Instance 3
Map 1 Map 2
804 924
0x76
(118)
1 or 3
3
97 18003 uint
RWES
Fi
Fi
Output Process (1
or 3)
Function Instance
Set the instance of
the function select-
ed above.
1 to 4 1 Instance 1
Map 1 Map 2
726 846
Instance 3
Map 1 Map 2
806 926
0x76
(118)
1 or 3
4
98 18004 uint
RWES
S.Lo
S.Lo
Output Process (1
or 3)
Scale Low
Set the scale low
for process output
in electrical units.
This value; in volts
or milliamps, will
correspond to 0%
PID power output or
range low retrans-
mit output.
-100.0 to 100.0 0.00 Instance 1
Map 1 Map 2
736 856
Instance 3
Map 1 Map 2
816 936
0x76
(118)
1 or 3
9
99 18009 float
RWES
S.hi
S.hi
Output Process (1
or 3)
Scale High
Set the scale high
for process output
in
electrical units. This
value; in volts or
milliamps, will cor-
respond to 100% PID
power output or
range high retrans-
mit output.
-100.0 to 100.0 10.00 Instance 1
Map 1 Map 2
738 858
Instance 3
Map 1 Map 2
818 938
0x76
(118)
1 or 3
0x0A
(10)
100 18010 float
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set