PMI Controller 130 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
A.Lg
A.Lg
Alarm (1 to 4)
Logic
Select what the
output condition
will be during the
alarm state.
AL.C Energize on
alarm (17)
AL.o De-energize on
alarm (66)
Close On
Alarm
Instance 1
Map 1 Map 2
1488 1888
Offset to
next in-
stance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
5
25 9005 uint
RWES
A.Sd
A.Sd
Alarm (1 to 4)
Sides
Select which side
or sides will trigger
this alarm.
both Both (13)
high High (37)
LoФІ Low (53)
Both Instance 1
Map 1 Map 2
1486 1886
Offset to
next in-
stance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
4
26 9004 uint
RWES
A.Lo
A.Lo
Alarm (1 to 4)
Low Set Point
If Type (Setup
Page, Alarm Menu)
is set to:
Process - set the
process value that
will trigger a low
alarm.
Deviation - set
the span of units
from the closed
loop set point
that will trigger
a low alarm. A
negative set point
represents a value
below closed
loop set point. A
positive set point
represents a value
above closed loop
set point.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
32.0°F
or units
0.0°C
Instance 1
Map 1 Map 2
1482 1882
Offset to
next in-
stance (Map
1 +50, Map
2 +60)
0x6D
(109)
1 to 4
2
18 9002 float
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set