PMI Controller • 154 • Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
ЛЏb.E
Mb.E
Communications (2)
Modbus TCP Enable
Activate Modbus
TCP.
yEs Yes (106)
no No (59)
Yes - - - - - - - - - - - - 17041 uint
RWE
EiP.E
EiP.E
Communications (2)
EtherNet/IP™ En-
able
Activate Ethernet/
IP™.
yEs Yes (106)
no No (59)
Yes - - - - - - - - - - - - 17042 uint
RWE
ao.nb
Ao.nb
Communications (2)
EtherNet/IP™ Out-
put Assembly
When using Ether-
Net/IP set the CIP
Implicit Assembly
Output Member
Quantity
1 to 20 20 - - - - - - - - - - - - 24009 uint
RWE
ai.nb
Ai.nb
Communications (2)
EtherNet/IP™ Input
Assembly
When using Ether-
Net/IP set the CIP
Implicit Assembly
Input Member Quan-
tity
1 to 20 20 - - - - - - - - - - - - 24010 uint
RWE
C_F
C_F
Communications (2)
Display Units
Select which scale
to use for tempera-
ture passed over
communications
port 2.
F °F (30)
C °C (15)
°F Instance 2
Map 1 Map 2
- - - - 2990
0x96
(150)
2
6
199 17050 uint
RWE
nU.S
nV.S
Communications (2)
Non-volatile Save
If set to Yes all
values written to
the control will be
saved in EEPROM.
The EEPROM allows
for approximately
one million writes.
yEs Yes (106)
no No (59)
No Instance 2
Map 1 Map 2
2514 2994
96 (150)
2
8
198 17051 uint
RWE
Note:
When changing IP address, the control power must be cycled for the new address to take effect.
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set