PMI Controller • 167 • Chapter 7 Profiling Page
Display Step Type Description Parameters in Step Type
ФІ.E
W.E
Step Types
Wait For Event
A Wait for Event Step will wait for the two Wait for Event states
(1 to 2) to match the specified state. The state of up to 2 event
outputs may be set or maintained.
ФІE.1 Wait Event 1
ФІE.2 Wait Event 2
Ent1 Event 1
Ent2 Event 2
ФІ.pr
W.Pr
Step Types
Wait For Process
A Wait for Process Step will wait for Process Value 1 or 2 to
match the Wait for Process Value. The state of up to 2 event
outputs may be set or maintained.
ФІ.p1 Wait for Process 1
ФІ.p2 Wait for Process 2
Ent1 Event 1
Ent2 Event 2
ФІ.bo
W.bo
Step Types
Wait For Both
A Wait For Process and Event Step will wait for Process Value 1
or 2 to match the Wait for Process 1 value, and/or the two Wait
Event states to match the specified state. The state of up to 2
event outputs may be set or maintained.
ФІ.p1 Wait for Process 1
ФІ.p2 Wait for Process 2
ФІE.1 Wait Event 1
ФІE.2 Wait Event 2
Ent1 Event 1
Ent2 Event 2
JL
JL
Step Types
Jump
A Jump step will repeat previous steps a number of times
designated in Jump Count. Jumps can be nested up to four
deep. The state of up to 2 event outputs may be set or main-
tained.
JS Jump Step
JC Jump Count
Ent1 Event 1
Ent2 Event 2
End
End
Step Types
End
An End Step will end the profile and set the control modes and
set points to match the End Type. The state of up to 2 event
outputs may be set or maintained. The event outputs will not
be set off unless specifically stated in this step. If a profile does
not have an End Step, the profile continues until step 40, then
stops and maintains the last set points and control modes.
End End Type
Ent1 Event 1
Ent2 Event 2