PMI Controller 229 • Chapter 11 Appendix
Indication Description Possible Cause(s) Corrective Action
No Serial Com-
munication
Cannot establish se-
rial communications
with the controller
Address parameter incor-
rect
Incorrect protocol se-
lected
Baud rate incorrect
Parity incorrect
Wiring error
EIA-485 converter issue
Incorrect computer or
PLC communications port
Incorrect software setup
Wires routed with power
cables
Termination resistor may
be required
Set unique addresses on
network
Match protocol between
devices
Match baud rate between
devices
Match parity between de-
vices
Correct wiring issue
Check settings or replace
converter
Set correct communica-
tion port
Correct software setup to
match controller
Route communications
wires away from power
wires
Place 120 Ω resistor
across EIA-485 on last
controller
Process
doesn’t con-
trol to set
point
Process is unstable
or never reaches
set point
Controller not tuned cor-
rectly
Control mode is incor-
rectly set
Control set point is incor-
rect
Perform autotune or
manually tune system
Set control mode appro-
priately (Open vs Closed
Loop)
Set control set point in
appropriate control mode
and check source of set
point: remote, idle, pro-
file, closed loop, open
loop
Temperature
runway
Process value con-
tinues to increase
or decrease past set
point.
Controller output incor-
rectly programmed
Thermocouple reverse
wired
Controller output wired
incorrectly
Short in heater
Power controller connec-
tion to controller defec-
tive
Controller output defec-
tive
Verify output function is
correct (heat or cool)
Correct sensor wiring
(red wire negative)
Verify and correct wiring
Replace heater
Replace or repair power
controller
Replace or repair control-
ler