PMI Controller • 43 • Chapter 2 Install and Wire
Warning:
ç
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may
result in damage to equipment
and property, and/or injury or
loss of life.
Note:
Maximum wire size termination
and torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination
or two 1.31 mm
2
(16 AWG)
• 0.56 Nm (5.0 in-lb.) torque
Note:
Adjacent terminals may be la-
beled differently, depending on
the model number
.
Note:
To prevent damage to the con-
troller, do not connect wires to
unused terminals.
Note:
Maintain electrical isolation
between digital input-outputs,
switched dc/open collector
outputs and process outputs to
prevent ground loops.
Note:
This equipment is suitable for
use in CLASS I, DIVISION 2,
Groups A, B, C and D or Non-
Hazardous locations only. Tem-
perature Code T4
Warning:
ç
Explosion Hazard – Substitution
of component may impair suit-
ability for
CLASS I, DIVISION 2.
Warning:
ç
Explosion Hazard - Do not dis-
connect while the circuit is live
or unless the area is known to be
free of ignitable concentrations
of flammable substances.
Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids,
etc.) with the mechanical relay,
solid state relay or open collector
output options requires use of an
R.C. suppressor.
Output 2, 4 NO-ARC Relay, Form A
common
normally open
L_
K_
Slot A, B
• 15A at 85 to 264VÅ
(ac) resistive load only
• 2,000,000 cycle rating
for NO-ARC circuit
• 100mA minimum load
• 2mA maximum off
state leakage
• Do not use on dc loads
• Output does not supply
power
Output 2: (L2, K2)
PM _ _ _ _ [H] - _ _ _ _
_ _ _
Output 4: (L4, K4)
PM [4, 8, 9] _ _ _ _ - _ _
_ [H] _ _ _
L
_
K
_
Output 2, 4 Mechanical Relay, Form A
common
mally open
L_
K_
• 5A at 240VÅ (ac) or
30VÎ (dc) maximum re-
sistive load
• 20mA at 24V minimum
load
• 125VA pilot duty @
120/240VÅ (ac), 25VA at
24VÅ (ac)
• 100,000 cycles at rated
load
• Output does not supply
power
• For use with ac or dc
See Quencharc note
Output 2: (L2, K2)
PM _ _ _ _ [J] - _ _ _ _ _
_ _
Output 4: (L4, K4)
PM _ _ _ _ _ - _ _ _ [J] _
_ _
L
_
K
_