Loading...
Watlow EZ-ZONE
®
PMI Controller 77 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Pa-
ram-
eter
ID
Data
Type
and
Ac-
cess
**
No Dis-
play
Monitor (1 to 2)
Set Point Active
Read the current ac-
tive set point.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
2172 2652
Instance 2
Map 1 Map 2
2252 2732
0x6B (107)
1 to 2
7
- - - - 8031 float
R
No Dis-
play
Monitor (1 to 2)
Autotune Status
Read the present
status of Autotune.
Off (62)
Waiting for cross 1
positive (119)
Waiting for cross 1
negative (120)
Waiting for cross 2
positive (121)
Waiting for cross 2
negative (122)
Waiting for cross 3
positive (123)
Waiting for cross 3
negative (150)
Measuring maximum
peak (151)
Measuring minimum
peak (152)
Calculating (153)
Complete (18)
Timeout (118)
- - - - Instance 1
Map 1 Map 2
1932 2412
Instance 2
Map 1 Map 2
2002 2482
0x97 (151)
1 to 2
0x1B (27)
- - - - 8027 uint
R
Loop
opEr
Control Loop Menu
r.En
r.En
Control Loop (1 to
2)
Remote Set Point
Enable this loop
to switch control
to the remote set
point.
no No (59)
yEs Yes (106)
No Instance 1
Map 1 Map 2
2200 2680
Instance 2
Map 1 Map 2
2280 2760
0x6B
(107)
1 to 2
0x15 (21)
48
7021 uint
RWES
C.ЛЏ
C.M
Control Loop (1 to
2)
Control Mode
Select the method
that this loop will
use to control.
off Off (62)
aUto Auto (10)
ЛЏan Manual (54)
Auto Instance 1
Map 1 Map 2
1880 2360
Instance 2
Map 1 Map 2
1950 2430
0x97
(151)
1 to 2
1
63
8001 uint
RWES
** R: Read, W: Write, E: EEPROM, S: User Set