Watlow EZ-ZONE
®
PMI Controller 76 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Pa-
ram-
eter
ID
Data
Type
and
Ac-
cess
**
L.st
L.St
Limit (1)
Limit Status *
Reflects whether
or not the limit is
in a safe or failed
mode..
faiL Fail (32)
safE Safe (1667)
- - - -
Instance 1
Map 1 Map 2
- - - - 744
0x70 (112)
1
0x0D (13)
- - - - 12013 uint
R
ЛЏon
opEr
Monitor Menu
C.ЛЏA
C.MA
Monitor (1 to 2)
Control Mode Ac-
tive
View the current
control mode.
off Off (62)
aUto Auto (10)
ЛЏan Manual (54)
- - - -
Instance 1
Map 1 Map 2
1882 2362
Instance 2
Map 1 Map 2
1952 2432
0x97 (151)
1 to 2
2
- - - - 8002 uint
R
h.pr
h.Pr
Monitor (1 to 2)
Heat Power
View the current
heat output level.
0.0 to 100.0% - - - -
Instance 1
Map 1 Map 2
1904 2384
Instance 2
Map 1 Map 2
1974 2454
0x97 (151)
1 to 2
0xD (13)
- - - - 8011 float
R
C.pr
C.Pr
Monitor (1 to 2)
Cool Power
View the current
cool output level.
-100.0 to 0.0% - - - -
Instance 1
Map 1 Map 2
1906 2386
Instance 2
Map 1 Map 2
1976 2456
0x97 (151)
1 to 2
0xE (14)
- - - - 8014 float
R
C.sp
C.SP
Monitor (1 to 2)
Closed-Loop Set
Point
View the working set
point currently in ef-
fect.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - - - - - - - - - - - - - 8029 float
R
pu.a
Pv.A
Monitor (1 to 2)
Process Value Ac-
tive
View the current fil-
tered process value
using the control
input.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
402 402
Instance 2
Map 1 Map 2
482 492
0x68 (104)
1 to 2
0x16 (22)
- - - - 8031 float
R
** R: Read, W: Write, E: EEPROM, S: User Set