95
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter Unit Description / Notes
P528 0.0 to 999
Process [ 100 ]
Variable Scale 0.1(< 100)
Factor 1 (> 99.9)
Defines the process variables scale. It makes the
conversion between percentage value (internally used
by the inverter) and the process variable unit
P528 defines how the process variable at P040 will
be showed:P040 = value % x P528.
Set P528 in:
P528 = full scale of used sensor (FM) x 100
P234
P536 0 to 1
Automatic [ 0 ]
Setting of P525 -
Allows the user to enable/disable a copy of P040
(process variable) in P525, when there is a
commutation of PID operation mode from manual to
automatic.
P536
0
1
Function
Active (copies the value of P040 in P525)
Inactive (does not copies thevalue of P040in P525)
Table 6.18 - P536 Configuration