104
APPENDIX
9
The following items are required for CE conformance:
1. The same as item 1 above.
2. The installation must provide a supply disconnecting
(isolation) device. A hand-operated supply
disconnecting device must be provided for each
income supply and be near to the equipment. This
device must disconnect the Soft-Starter from the supply
when required (e. g. during work on the electrical
equipment). See EN60204-1, 5.3. Specify the current
and voltage of this disconnecting device according to
the data given in the item 8.1 and 8.2.
DANGER!
This equipment must not be used as an emergency stop
mechanism (See EN60204, 9.2.5.4).
9.1.2.2 Low Voltage
Directive (LVD)
(1) The cables shielding must be solidly connected to the
common backplane, using preferably a bracket.
The backplane must be electrically conductive (have no
paint).
Figure 9.1 - Soft-Starter SSW-03 Plus connections
(1)
SSW-03 PLUS