110
APPENDIX
9
9.7 - RECOMMENDED APPLICATION WITH TERMINALS FOR THREE
WIRE CONTROL AND MOTOR SPEED REVERSAL
Obs.: It's necessary to use normal fuses or breaker to protect
the installation. Ultra-Fast fuses are not necessary for
the SSW-03 Plus operation, but they are recommended
for SCR protection.
The transformer "T" is optional and must be utilized
when the line voltage is different than the electronics
and fan voltage.
For the integral motor protection it's recommended to
install one or more thermostats in the motor. If the ther-
mostat is not used, the external input error (DI3) from
SSW-03 Plus must be connected to +Vdc.
NOTE!
A contactor in the mains input (see 9.4) is necessary to pro-
tect the motor in case there is a phase failure which is caused
by damage in the SSW-03 Plus power circuit with the appli-
cations of the power isolation contactor.
Parameter Program
P04 OFF
P51 3
P53 4
P54 4
P55 3
P61 OFF
OPTIONAL
START
STOP
ROTATION
DIRECTION
EMERGENCY
OPTIONAL
PLUS

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WEG SSW-03 Plus Series and is the answer not in the manual?

WEG SSW-03 Plus Series Specifications

General IconGeneral
BrandWEG
ModelSSW-03 Plus Series
CategoryController
LanguageEnglish

Related product manuals