1. Parameters
Para- Function Adjustable Factory User's Page
meter Range Setting Setting
Permits parameter
changing
P00
P01
P02
P03
P04
P11
P12
P13
P14
P15
P21
P25
P26
P27
OFF, ON
25...90% UN
1...240 s
100... 40%UN
OFF,2...240s
OFF,150...500%IN
32...200%IN
OFF, 1...20s
20...190%IN
OFF, 1...200s
OFF, 30.0...200.0%IN
5, 10, 15, 20, 25, 30
0.80...1.50
OFF, 1...600s
OFF
30%UN
20s
100%UN
OFF
OFF
120%IN
OFF
70%IN
OFF
OFF
30
1.00
OFF
58
58
59
59
60
60
62
64
63
64
84
85
89
90
Overload class
Service factor
Auto-reset of the
thermal memory
Regulation Parameter
Motor Parameter
Initial Voltage
Acceleration ramp
time
Voltage fall step
during deceleration
Ramp time during
deceleration
Current limit during
starting
Immediate overcurrent
Immediate overcurrent
time
Immediate undercur-
rent
Immediate undercur-
rent time
Motor current setting