Οδηγίες εγκατάστασης και λειτουργίας Wilo-Control EC/ECe-Booster 391
Holding register
(Protocol)
Name Data type Scale & unit Elements Access* Added
0.1 h
0.1 psi
40041
(40)
Pump 1 mode ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40042
(41)
Pump 2 mode ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40043
(42)
Pump 3 mode ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40062
(61)
Switch box state BITMAP 0: SBM
1: SSM
R 31.000
40139 - 40140
(138-139)
Error state BITMAP32 0: Sensor error
1: P max
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6
Alarm
11: -
12: -
13: Frost
14: Battery Low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave
communication
20: Net supply
21: Leakage
R 31.000
40141
(140)
Acknowledge BOOL W 31.000
40142
(141)
Alarm history index UINT16 RW 31.000
40143
(142)
Alarm history error
code
UINT16 0.1 R 31.000