EasyManua.ls Logo

Wolf BWL-1S-07 - 14 Routing the Refrigerant Lines

Wolf BWL-1S-07
120 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3064298_201805 25
Routingtherefrigerantlines
14 Routingtherefrigerantlines
Theoutdoormoduleispre-chargedwithrefrigerantR410A.
No additional charge is required for lines up to 12 m in length.
Minimumlinelength3m,maximumlinelength25m.
Max.heightdifferentialbetweenindoorandoutdoorunit15m.
For12–25mlinelength,topupwith60g/mofrefrigerantR410A.
Use only copper pipes suitable for refrigerants to EN-12735-1, and thermal insulation with a temperature resistance
ofupto120°C.(Forinternaldiameter,see"Specication"chapter.)
Suction gas lines and liquid lines must have separate thermal insulation. Closed cell, diffusion-proof thermal
insulation, min. thickness 6 mm.
Extended refrigerant lines are not permitted for outdoor use. Junctions must remain accessible for leak testing,
as they are potential leak sources.
Riskofinjuryfromincorrectlyroutedpipework
Route pipework in such a way as to avoid any danger to persons.
Before routing pipework, please note:
Wherepipeworkisroutedviaductswithothersupplylines,forexample,hotuepipes,areciprocal
effect can result. Insulate supply lines where necessary.
Do not route pipework through lift shafts.
In public stairways and passageways, route pipework at a minimum height of 2.20 m.
Pipeworkroutedthroughre-resistantwallsandceilingsmusthavereproofseals.
Protect pipework from excessive stress.
Protectpipeworkfromenvironmentalinuences,suchasdirt,waste,andwater.
Damagefromimpuritiesintherefrigerantcircuit
Moisture or dirt, for example metal swarf, can get into the refrigerant circuit.
Never reuse refrigerant lines.
Use only closed refrigerant lines.
Pipes in wall ducts must be plugged.
Pipeworkdamagedbykinking
Copper pipes kink easily and can then no longer be used.
Never step on copper pipes.
Always choose an adequately large bending radius; use a pipe bender.
Install pipe supports every 2 m.
Use protective piping for ground routing.
Structuraldamagefromcondensate
Where pipework is not insulated or its thermal insulation is damaged, condensate forms.
Thermally insulate all pipework.
Check that the pipework is fully insulated and that all junctions are lagged with insulating tape.
Lag damaged thermal insulation using insulating tape (accessory).
Seal wall ducts on site.
Please
note
Please
note
Please
note

Table of Contents

Other manuals for Wolf BWL-1S-07

Related product manuals