Connectingtheheating/DHWcircuit
17.1.4 Drainingtheheatingsystem
- Shut down the system.
Riskofscalding
Hot water can cause severe scalding. Before working on water-seated parts, allow the appliance to
cool to below 40 °C, shut off all valves and, if necessary, drain the appliance.
Riskofburns
Hot components can cause burns. Before working on the opened up appliance, allow it to cool to
below 40 °C or wear suitable gloves.
Dangerfromoverpressureonthewaterside
Overpressure on the water side can cause severe injuries. Before working on water-seated parts,
allow the appliance to cool to below 40 °C, shut off all valves and, if necessary, drain the appliance.
Note: Sensors can be water-based and therefore pressurised.
- Safeguard the heating system against accidental reconnection of the power supply.
- Openthedrain&llvalve(BDFvalve),forexampleontheindoormodule.
- Open the air vent valves in the heating circuits.
- Drain off the heating water.
17.1.5 Overowvalve
Ifnoseparatingcylinderisbeingused,theminimumheatingwaterowratecanbeensuredbymeans
ofanoverowvalve.
17.1.6 DHWheating
Do not operate via the buffer cylinder.
17.1.7 Circulationpump
Anelectronicallyregulatedhighefciencypumpisintegratedintotheindoormodule.
17.1.8 Hydraulicseparatingcylinder(lowlossheader)
Used when there are several heating circuits.
17.1.9 Maximumthermostat(MaxTh)
Toprotectareaheatingsystems(e.g.underoorheatingcircuits)fromexcessivelyhighowtemperatures,
temperature limiters or maximum thermostats are required.
The oating contacts of maximum thermostats and, where applicable, dew point monitors, can be
connected in series and connected to the programmable input E1.
When the contact opens, the heat generator and heating circuit pump are switched OFF.
17.1.10 Thefollowingparametersarecriticalforthetransferoftheheatpumpoutputto
theheatingsystem:
- The heatingwaterowrate(m
.
) in m
3
/h(nominalowrate)
- The temperaturedifferentialbetweentheowandreturn(∆t)
- The specicheatcontentofthewater(c)
Q
HP
=mxcx∆t(kW)
.
.
17.1.11 Pipedimensions
- Thepipedimensionsmustbematchedtothenominalowrate.
- Ensure that the system is vented correctly.
- Flush the system.