Systemcongurations
29 Systemcongurations
Overview
ThefollowingsystemcongurationscanbeperformedforoperatingtheBWL-1SandBWL-1SB.
Contractor
Parameter
Meaning Setting range Factory
setting
Individual
setting
System
WP001 Systemconguration 01, 02, 05, 11, 12, 14,
15, 33, 34, 51, 52
01
Systemcong. Description
01 Cylinder in series, one heating circuit, DHW heating, active cooling possible
(in conj. with additional 3-way diverter valve for cooling)
02 Cylinder in series, DHW heating, can be extended with mixer circuits,
can be extended with solar circuit
05 Cylinder in series via 3-way valve, one heating circuit, DHW heating,
can be extended with solar circuit, active cooling possible
11 Separating cylinder, one heating circuit, DHW heating
12 Solidfuelboiler/TOB,straticationcylinderBSP-W/BSP-W-SL/BSH,DHWheating,
can be extended with mixer circuits, can be extended with solar circuit
14 Solidfuelboiler/TOB,straticationcylinderBSP-W/BSP-W-SL/BSH,DHWheating,
can be extended with mixer circuits, can be extended with solar circuit, active cooling possible
15 Separating cylinder, one heating circuit, DHW heating, can be extended with mixer circuits,
can be extended with solar circuit, active cooling possible
33 Separating cylinder, CGB-2 ..., heating circuit downstream of low loss header, DHW heating,
can be extended with mixer circuits, can be extended with solar circuit
34 TOB,straticationcylinder,BSH,BSP-W,BSP-W-SL,DHWheating,canbeextendedwith
mixer circuits, can be extended with solar circuit
51 0 - 10 V activation for external demand (e.g. by building management system (BMS)),
central heating, DHW heating, active cooling possible
52 ON/OFF activation for external demand (e.g. by building management system (BMS)),
central heating, DHW heating
Theentiresystemmustberestarted(poweroff/poweron)eachtimeachangeismadetotheconguration.
Note:
Hydraulic diagrams and electrical details can be found on the WOLF homepage and in the"HydraulicSystem
Solutions" technical guide.