54 3064298_201805
AMdisplaymodule
24.5 Description
(Selection and more details in the AM display module instructions.)
24.5.1 DHWoperatingmode
Comfort setting:
In the Comfort setting, the heat pump tries to reach the set DHW temperature.
After the delay period (WP013/WP023) has elapsed, the electric heater/additional heat generator is activated.
When the compressor's application limit is reached (FL/RTN > max.), the electric heater/additional heat generator
continues the heating process until the set DHW temperature is reached.
If the maximum cylinder heating time is exceeded, DHW mode is interrupted for the duration of the set maximum
cylinder heating time (WP022).
ECO setting:
In the ECO setting, the heat pump tries to reach the selected set DHW temperature or set minimum DHW temperature.
After the delay period (WP013/WP023) has elapsed, the electric heater/additional heat generator is activated.
When the compressor's application limit is reached (FL/RTN > max.), the electric heater/additional heat generator
continues the heating process until the set minimum DHW temperature is achieved.
If the maximum cylinder heating time is exceeded, DHW mode is terminated, provided the set minimum DHW
temperature has already been achieved.
Otherwise DHW mode is interrupted for the duration of the set maximum cylinder heating time (WP022).
24.5.2 DHWquickheat-up
If the DHW quick heat-up standard setting is on, the DHW temperature is regulated once to the set DHW temperature
conguredontheAM/BM-2,usingallavailableheatgenerators.Thestandardsettingisthenautomaticallyreset.
24.6 Energysavingmode
No function.
24.6.1 Activecooling
Enables the user to activate/deactivate active cooling.
This requires, amongst other things, that the system is congured with active cooling and that active cooling is
enabled via contractor parameter WP058 (factory setting: OFF).
(See chapter "Additional functions".)