Contractorparameters
Contractor
Parameter
BM-2designation AMdesignation Settingrange Factory
setting
WP033 Cooling with PV/SG Cooling with PV/SG OFF, ON OFF
Activecooling
WP053 T_outs. enable Coolg Outside temp. to enable cooling 15.0 ... 40.0 °C 25.0 °C
WP054 Minowtcooling Min.owtemp.forcooling 5.0 ... 25.0 °C 20.0 °C
WP055 OffsetsetowCoolg Offsetforsetowtemp.,cooling 5.0 ... 40.0 °C 15.0 °C
WP058 Enable act. cooling Enable active cooling OFF, ON OFF
Nightmode
WP061 Night mode end Night mode end 00:00 ... 23:59 06:00
WP062 Night mode start Night mode start 00:00 ... 23:59 22:00
WP064
Night mode limit
Night mode limitation
75 %, 65 %, 55 %,
45 %
75 %
WP066 Night mode Night mode OFF, ON OFF
Compressor
WP080 Comp. dual mode pt Compressor dual mode point -20.0 °C ... 45.0 °C -20.0 °C
Electric heater/add HG
WP090 Enable elec heating Enable electric heater
(heating mode)
OFF, ON ON
WP091 Dual mode pt el htg Elec heater dual mode pt
(heating mode)
-20.0 °C ... 45.0 °C -5.0 °C
WP092 Power-OFF elec htg Power-OFF for elec. heater OFF, ON ON
WP093 Temp. deact. WP091 Temporary deactivation of WP091 0 to 40 days 0 days
WP094 Electric heater type Electric heater type None, 2 kW, 3 kW,
4 kW, 6 kW, 9 kW
6 kW
WP101 Dual md pt, add HG Add HG dual mode point
(heating mode)
-20.0 °C ... 45.0 °C 0.0 °C
WP104 Add HG eBUS Add HG via eBUS OFF, ON OFF
Other
WP121 Max. compressor
starts/h
Max. compressor starts per hour 3 ... 10 / h 6 / h