Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 163/174
Parameter Setting range Default value Customer setting
BREAKER CONFIGURATION
Configure breaker
YES/NO NO Y N Y N
Breaker logic:
EXTERNAL [EXT]
PARALLEL [PAR]
OPEN TRANSIT [OPEN]
CLOSED TRANSIT [CLOSE]
INTERCHANGE [CHANG]
PARALLEL EXT
PAR
OPEN
CLOSE
CHANG
EXT
PAR
OPEN
CLOSE
CHANG
Add-on/off ramp max.time
0 to 999 s 20 s
Open GCB with F2 max.time
0 to 999 s 10 s
GCB close.relay
Impulse [I]
Constant [C]
Constant I
C
I
D
GCB open relay
NO-contact [NO]
NC-contact [NC]
NO-contact NO
NC
NO
NC
synch
Synchronize df max
0.02 to 0.49 Hz 0.20 Hz
..
Synchronize df min
0.0 to 0,49 Hz -0.10 Hz
..
Synchronize dV max
1.0 to 20.0 % 2.0 %
..
Synchronize time pulse>
0.02 to 0.26 s 0.24 s
..
Closing time GCB
40 to 300 ms 80 ms
synch
Closing time MCB
40 to 300 ms 80 ms
RPQ
Phase matching
ON/OFF ON on off on off
..
Phase matching gain
1 to 36 2
..
Phase matching df start
0.02 to 0.25 Hz 0,20 Hz
..
Detection Mains connected <
1 to 15 ° 5 °
RPQ
Detection Mains conn. after
0 to 999 s 10 s °
synch
Automat.breaker deblocking
ON/OFF OFF on off on off
..
Sync.time contr.
ON/OFF ON on off on off
..
Sync.time contr. delay
10 to 999 s 180 s
L
GCB dead bus op.
ON/OFF ON on off on off
..
GCB dead bus op. df max
0.05 to 5.00 Hz 2.0 Hz
..
GCB dead bus op. dV max.
1.0 to 15.0 % 10.0 %
..
GCB dead bus op max.time
0 to 999 s 30 s
synch
MCB dead bus op.
ON/OFF ON on off on off
induct.
Switching-on GCB
ON/OFF ON on off on off
..
Switching-on GCB df max
0.05 to 9.99 Hz 0.20 Hz
..
Switching-on GCB df min
0.0 to
-
9.99 Hz -0.10 Hz
..
Switching-on GCB T.impuls >
0.02 to 0.26 s 0.24 s
..
Automat.breaker deblocking
ON/OFF ON on off on off
..
Switch.time cntr
ON/OFF ON on off on off
induct.
Switch.time cntr delay
2 to 999 s 180 s
Supervision GCB
ON/OFF ON on off on off
Supervision MCB
ON/OFF ON on off on off
GCP31
Mains decoupling via
GCB [GCB]
GCB->EXT [GCB>EX]
EXT [EXT]
EXT->GCB [EX>GCB]
GCB
GCB
GCB>EX
EXT
EX>GCB
GCB
GCB>EX
EXT
EX>GCB
GCP32
Mains decoupling via
GCB [GCB]
GCB->MCB [GCB>MC]
MCB [MCB]
MCB->GCB [MC>GCB]
GCB
GCB
GCB>MC
MCB
MC>GCB
GCB
GCB>MC
MCB
MC>GCB
L
Mains decoupling -> after
0.10 to 5.00 s 0.14 s
Switch MCB in STOP mode
YES/NO NO Y N Y N
EMERGENCY POWER CONFIGURATION
Configure emergency
YES/NO NO Y N Y N
Emergency power
ON/OFF ON on off on off
Emergency power start del.
0.5 to 99.9 s 3.0 s