Manual 37278B GCP-30 Series - Genset Control
Page 164/174 © Woodward
Parameter Setting range Default value Customer setting
MONITORING CONFIGURATION
Configure monitoring
YES/NO NO Y N Y N
Gen.power monit.
ON/OFF OFF on off on off
Gen.power monit. resp.val1
0 to 9,999 kW 100 kW
Gen.power monit. hyst.lv1
0 to 999 kW 10 kW
Gen.power monit. delay lv1
0 to 650 s 1 s
Gen.power monit. resp.val2
0 to 9,999 kW 120 kW
Gen.power monit. hyst.lv2
0 to 999 kW 10 kW
Gen.power monit. delay lv2
0 to 650 s 1 s
Mains power mon.
ON/OFF OFF on off on off
Mains power mon. res.val.
I/E 0 to 9,999 kW E100 kW
Mains power mon. hysteresis
0 to 999 kW 10 kW
Mains power mon. delay
0 to 650 s 1 s
Overload monit.
ON/OFF OFF on off on off
Gen.overload MOP resp.value
80 to 150 % 120 %
Gen.overload MOP delay
0 to 99 s 1 s
Gen.overload IOP resp.value
80 to 150 % 105 %
Gen.overload IOP delay
0 to 99 s 1 s
Rev./red.power monitoring
ON/OFF OFF on off on off
Rev./red.power resp.value
-99 to+99 % -10 %
Rev./red.power delay
0,0 to 9,9 s 1.0 s
Load unbalanced
ON/OFF OFF on off on off
Load unbalanced max.
0 to 100 % 30 %
Load unbalanced delay
0.02 to 9.98 s 1.00 s
Gen.overcurrent monitoring
ON/OFF OFF on off on off
Gen.overcurrent limit 1
0 to 300 % 110 %
Gen.overcurrent delay 1
0.02 to 9.98 s 1.00 s
Gen.overcurrent limit 2
0 to 300 % 120 %
Gen.overcurrent delay 2
0.02 to 9.98 s 0.04 s
Gen.overcurrent Cool down
ON/OFF OFF on off on off
Gen.frequency- monitoring
ON/OFF ON on off on off
Gen.overfreq. f >
50.0 to 140.0 % 110.0 %
Gen.overfreq. delay
0.02 to 9.98 s 0.30 s
Gen.underfreq. f <
50.0 to 140.0 % 90.0 %
Gen.underfreq. delay
0.02 to 9.98 s 0.30 s
Engine overspeed >
0 to 9,999 rpm 1,900 rpm
Gen.voltage monitoring
ON/OFF ON on off on off
Gen.overvoltage U >
20.0 to 150.0 % 110.0 %
Gen.overvoltage delay
0.02 to 9.98 s 0.30 s
Gen.undervoltage U <
20.0 to 150.0 % 90.0 %
Gen.undervoltage delay
0.2 to 9.98 s 0.30 s
Mains frequency monitoring
ON/OFF ON on off on off
Mains overfreq. f >
80.0 to 140.0 % 110.0 %
Mains overfreq. delay
0.02 to 9.98 s 0.06 s
Mains underfreq. f <
80.0 to 140.0 % 90.0 %
Mains underfreq. delay
0.02 to 9.98 s 0.06 s
Mains voltage monitoring
ON/OFF ON on off on off
Mains overvolt. U >
20.0 to 150.0 % 110.0 %
Mains overvolt. delay
0.02 to 9.98 s 0.06 s
Mains undervolt. U <
20.0 to 150.0 % 90.0 %
Mains undervolt. delay
0.02 to 9.98 s 0.06 s
Phase shift monitoring
ON/OFF ON on off on off
Monitoring
one-phase [1]
three-phase [3]
three-phase 1 3 1 3
Phase shift one-phase
3 to 30 ° 12 °
Phase shift three-phase
3 to 30 ° 8 °
Mains settling time
0- to 999 s 10 s
Batt.undervolt. U <
9.5 to 30.0 V 10.0 V
Batt.undervolt. delay
0 to 99 s 10 s
Horn self reset
1 to 9,999 s 180 s