Parameter List
3
3.5 b: Application
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING 103
No.
(Hex.)
Name Description
Default
(Range)
b5-12
(01B0)
Feedback Loss Detection
Select
Sets the drive response to PID feedback loss/excess. Sets drive operation after the drive detects PID
feedback loss/excess.
0 : Digital Out Only, Always Detect
1 : Alarm + Digital Out, Always Det
2 : Fault + Digital Out, Always Det
3 : Digital Out Only, @ PID Enable
4 : Alarm + Digital Out, @PID Enable
5 : Fault + Digital Out, @PID Enable
0
(0 - 5)
b5-13
(01B1)
PID Feedback Loss
Detection Lvl
Sets the level that triggers PID Feedback Loss [FbL] detection as a percentage of the Maximum
Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
0%
(0 - 100%)
b5-14
(01B2)
PID Feedback Loss
Detection Time
Sets the length of time that PID Feedback must be less than b5-13 [PID Feedback Loss Detection
Lvl] to detect PID Feedback Loss [FbL].
1.0 s
(0.0 - 25.5 s)
b5-15
(01B3)
PID Sleep Function Start
Level
Sets the output level that triggers the PID Sleep function. Determined by A1-02
(0.0 - 590.0)
b5-16
(01B4)
PID Sleep Delay Time Sets a delay time to start or stop the PID Sleep function. 0.0 s
(0.0 - 25.5 s)
b5-17
(01B5)
RUN
PID Accel/Decel Time Raises or lowers the PID setpoint using the acceleration and deceleration times set to the drive. This
is a soft-starter for the PID setpoint.
0.0 s
(0.0 - 6000.0 s)
b5-18
(01DC)
b5-19 PID Setpoint Selection Sets the function that enables and disables b5-19 [PID Setpoint Value].
0 : Disabled
1 : Enabled
0
(0, 1)
b5-19
(01DD)
RUN
PID Setpoint Value Sets the PID setpoint when b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled]. 0.00%
(0.00 - 100.00%)
b5-20
(01E2)
PID Unit Selection Sets the number of digits to set and show the PID setpoint.
0 : 0.01Hz units
1 : 0.01% units
2 : rev/min
3 : User Units
1
(0 - 3)
b5-34
(019F)
RUN
PID Output Lower Limit
Level
Sets the lower limit level for the PID control as a percentage of E1-04 [Maximum Output
Frequency].
When you use b5-34, set b5-91 = 0 [EZ Sleep Minimum Speed = 0 (Disabled)].
When you set the output lower limit level as Hz units or min
-1
(r/min) units, refer to page Missing
reference ID.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
0.0%
(-100.0 - +100.0%)
b5-35
(01A0)
RUN
PID Input Limit Level Sets the output upper limit for the PID control as a percentage of the Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
1000.0%
(0.0 - 1000.0%)
b5-36
(01A1)
PID High Feedback
Detection Lvl
Sets the level that triggers Excessive PID Feedback [FbH] as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
100%
(0 - 100%)
b5-37
(01A2)
PID High Feedback
Detection Time
Sets the length of time that the PID feedback signal must be more than the level set in b5-36 [PID
Feedback High Detection Lvl] to cause Excessive PID Feedback [FbH].
1.0 s
(0.0 - 25.5 s)
b5-38
(01FE)
PID User Unit Display
Scaling
Sets the value that the drive sets or shows as the PID setpoint when at the maximum output
frequency.
Determined by b5-20
(1 - 60000)