3.7 d: Reference Settings
112 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
No.
(Hex.)
Name Description
Default
(Range)
d1-15
(0290)
RUN
Reference 15 Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-16
(0291)
RUN
Reference 16 Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-17
(0292)
RUN
Jog Reference Sets the Jog frequency reference in the units from o1-03 [Frequency Display Unit Selection]. Set H1-
xx = 6 [MFDI Function Select = Jog Reference Selection] to use the Jog frequency reference.
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
6.00 Hz
(0.00 - 590.00 Hz)
◆ d2: Reference Limits
No.
(Hex.)
Name Description
Default
(Range)
d2-01
(0289)
Frequency Reference Upper
Limit
Sets maximum limit for all frequency references. The maximum output frequency is 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Motor Max Revolutions]
100.0%
(0.0 - 110.0%)
d2-02
(028A)
Frequency Reference Lower
Limit
Sets minimum limit for all frequency references. The maximum output frequency is 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Motor Max Revolutions]
0.0%
(0.0 - 110.0%)
d2-03
(0293)
Analog Frequency Ref
Lower Limit
Sets the lower limit for the master frequency reference (the first frequency of the multi-step speed
reference) as a percentage. The maximum output frequency is 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
0.0%
(0.0 - 110.0%)
◆ d3: Jump Frequency
No.
(Hex.)
Name Description
Default
(Range)
d3-01
(0294)
Jump Frequency 1 Sets the median value of the frequency band that the drive will avoid. 0.0 Hz
(Determined by A1-02)
d3-02
(0295)
Jump Frequency 2 Sets the median value of the frequency band that the drive will avoid. 0.0 Hz
(Determined by A1-02)
d3-03
(0296)
Jump Frequency 3 Sets the median value of the frequency band that the drive will avoid. 0.0 Hz
(Determined by A1-02)
d3-04
(0297)
Jump Frequency Width Sets the width of the frequency band that the drive will avoid. 1.0 Hz
(Determined by A1-02)