3.13 o: Keypad-Related Settings
164 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
No.
(Hex.)
Name Description
Default
(Range)
o2-23
(11F8)
RUN
External 24V Powerloss
Detection
Sets the function to give a warning if the backup external 24 V power supply turns off when the main
circuit power supply is in operation.
0 : Disabled
1 : Enabled
0
(0, 1)
o2-26
(1563)
Alarm Display at Ext. 24V
Power
When you connect a backup external 24 V power supply, this parameter sets the function to trigger
an alarm when the main circuit power supply voltage decreases.
Note:
The drive will not run when it is operating from one 24-V external power supply.
0 : Disabled
1 : Enabled
1
(0, 1)
o2-27
(1565)
bCE Detection Selection Sets drive operation if the Bluetooth device is disconnected when you operate the drive in Bluetooth
Mode.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
3
(0 - 4)
o3: Copy Keypad Function
No.
(Hex.)
Name Description
Default
(Range)
o3-01
(0515)
Copy Keypad Function
Selection
Sets the function that saves and copies drive parameters to a different drive with the keypad.
0 : Copy Select
1 : Backup (drive keypad)
2 : Restore (keypad drive)
3 : Verify (check for mismatch)
4 : Erase (backup data of keypad)
0
(0 - 4)
o3-02
(0516)
Copy Allowed Selection Sets the copy function when o3-01 = 1 [Copy Keypad Function Selection = Backup (drive
keypad)].
0 : Disabled
1 : Enabled
0
(0, 1)
o3-04
(0B3E)
Select Backup/Restore
Location
Sets the storage location for drive parameters when you back up and restore parameters. This
parameter is only available when using an LCD keypad.
0 : Memory Location 1
1 : Memory Location 2
2 : Memory Location 3
3 : Memory Location 4
0
(0 - 3)
o3-05
(0BDA)
Select Items to Backup/
Restore
Sets which parameters are backed up, restored, and referenced. This parameter is only available when
using an LCD keypad.
0 : Standard Parameters
1 : Standard + DWEZ Parameters
1
(0, 1)
o3-06
(0BDE)
Auto Parameter Backup
Selection
Sets the function that automatically backs up parameters. This parameter is only available when
using an LCD keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
o3-07
(0BDF)
Auto Parameter Backup
Interval
Sets the interval at which the automatic parameter backup function saves parameters from the drive
to the keypad.
Note:
This parameter is only available when using an LCD keypad.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
1
(0 - 3)