3.6 C: Tuning
110 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
No.
(Hex.)
Name Description
Default
(Range)
C5-12
(0386)
Integral Operation @ Accel/
Decel
Sets ASR integral operation during acceleration and deceleration.
0 : No
1 : Yes
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train
Function = Speed Feedback (V/F Control)] to enable this parameter.
0
(0, 1)
C5-29
(0B18)
Expert
Speed Control Response Sets the level of speed control responsiveness. Usually it is not necessary to change this setting.
0 : Standard
1 : High Performance 1
1
(0, 1)
C5-39
(030D)
ASR Primary Delay Time
Const 2
Sets the filter time constant used when the torque reference is output from ASR. Usually it is not
necessary to change this parameter.
0.000 s
(0.000 - 0.500 s)
C6: Duty & Carrier Frequency
No.
(Hex.)
Name Description
Default
(Range)
C6-01
(0223)
Normal / Heavy Duty
Selection
Sets the drive duty rating.
0 : Heavy Duty Rating
1 : Normal Duty Rating
1
(0, 1)
C6-02
(0224)
Carrier Frequency Selection Sets the carrier frequency for the transistors in the drive.
1 : 2.0 kHz
2 : 5.0 kHz (AOLV/PM: 4.0 kHz)
3 : 8.0 kHz (AOLV/PM: 6.0 kHz)
4 : 10.0 kHz (AOLV/PM: 8.0 kHz)
5 : 12.5 kHz (AOLV/PM: 10.0 kHz)
6 : 15.0 kHz (AOLV/PM: 12.0 kHz)
7 : Swing PWM4 (Audible Sound 1)
8 : Swing PWM4 (Audible Sound 2)
9 : Swing PWM4 (Audible Sound 3)
A : Swing PWM4 (Audible Sound 4)
B : Leakage Current Rejection PWM
F : User Defined (C6-03 to C6-05)
Note:
The setting range changes when the A1-02 [Control Method Selection] value changes:
5, 8 [OLV/PM, EZOLV]: You can set C6-02 = 1 to 6, B, and F.
6 [AOLV/PM]: You can set C6-02 = 1 to 6.
The carrier frequency for Swing PWM 1 is equivalent to 2.0 kHz. Swing PWM applies a
special PWM pattern to decrease the audible noise.
Determined by A1-02, C6-
01, and o2-04
(Determined by A1-02)
C6-03
(0225)
Carrier Frequency Upper
Limit
Sets the upper limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
C6-04
(0226)
Carrier Frequency Lower
Limit
Sets the lower limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
C6-05
(0227)
Carrier Freq Proportional
Gain
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier Frequency Selection =
User Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(0 - 99)
C6-09
(022B)
Carrier Freq at Rotational
Tune
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to change this setting.
0 : 5 kHz
1 : Use C6-03
0
(0, 1)