EasyManuals Logo

YASKAWA GA500 Maintenance & Troubleshooting

YASKAWA GA500
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #152 background imageLoading...
Page #152 background image
3.11 L: Protection Functions
152 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
No.
(Hex.)
Name Description
Default
(Range)
L7-07
(04C9)
Torque Limit during Accel/
Decel
Sets the torque limit function during acceleration and deceleration.
0 : Proportional only
1 : Proportional & Integral control
0
(0, 1)
L7-16
(044D)
Torque Limit Process at Start Assigns a time filter to allow the torque limit to build at start.
0 : Disabled
1 : Enabled
1
(0, 1)
L8: Drive Protection
No.
(Hex.)
Name Description
Default
(Range)
L8-01
(04AD)
3% ERF DB Resistor
Protection
Sets the function to enable braking resistor protection with a Yaskawa ERF series braking resistor
(3% ED) installed on the heatsink.
0 : No
1 : Yes
0
(0, 1)
L8-02
(04AE)
Overheat Alarm Level Sets the oH detection level in temperature. Determined by o2-04, C6-01
(50 - 150 °C)
L8-03
(04AF)
Overheat Pre-Alarm
Selection
Sets operation after the drive detects an oH alarm.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Operate at Reduced Speed (L8-19)
3
(0 - 4)
L8-05
(04B1)
Input Phase Loss Protection
Sel
Sets the function to enable and disable input phase loss detection.
0 : Disabled
1 : Enabled
Determined by o2-04
(Determined by o2-04)
L8-07
(04B3)
Output Phase Loss
Protection Sel
Sets the function to enable and disable output phase loss detection. The drive starts output phase loss
detection when the output current decreases to less than 5% of the drive rated current.
Note:
The drive can incorrectly start output phase loss detection in these conditions:
The motor rated current is very small compared to the drive rating.
The drive is operating a PM motor with a small load.
0 : Disabled
1 : Fault when one phase is lost
2 : Fault when two phases are lost
1
(0 - 2)
L8-09
(04B5)
Output Ground Fault
Detection
Sets the function to enable and disable ground fault protection.
0 : Disabled
1 : Enabled
Determined by o2-04
(0, 1)
L8-10
(04B6)
Heatsink Fan Operation
Selection
Sets operation of the heatsink cooling fan.
0 : During Run, w/ L8-11 Off-Delay
1 : Always On
2 : Temperature-Dependent Fan Ctrl.
0
(0 - 2)
L8-11
(04B7)
Heatsink Fan Off-Delay
Time
Sets the length of time that the drive will wait before it stops the cooling fan after it cancels the Run
command when L8-10 = 0 [Heatsink Fan Operation Selection = During Run, w/ L8-11 Off-Delay].
60 s
(0 - 300 s)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
Note:
The setting range changes when the L8-35 [Installation Method Selection] value changes:
0 [IP20/UL Open Type]: -10 °C to +60 °C
1 [Side-by-Side Mounting]: -10 °C to +50 °C
2 [IP20/UL Type 1]: -10 °C to +50 °C
3 [External Heatsink/Finless]: -10 °C to +50 °C
40 °C
(-10 °C - +60 °C)
L8-15
(04BB)
Drive oL2 @ Low Speed
Protection
Sets the function to decrease the drive overload level at which the drive will trigger oL2 [Drive
Overload] during low speed operation (6 Hz or slower) to prevent damage to the main circuit
transistors.
Note:
Contact Yaskawa or your nearest sales representative before disabling this function at low
speeds. If you frequently operate drives with high output current in low speed ranges, it can cause
heat stress and decrease the life span of drive IGBTs.
0 : Disabled (No Additional Derate)
1 : Enabled (Reduced oL2 Level)
1
(0, 1)

Table of Contents

Other manuals for YASKAWA GA500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA GA500 and is the answer not in the manual?

YASKAWA GA500 Specifications

General IconGeneral
SeriesGA500
Overload Capacity150% for 60 seconds, 200% for 3 seconds
EnclosureIP20
Control MethodV/f Control
BrakingDynamic Braking
CommunicationEthernet/IP, Modbus RTU, Modbus TCP, DeviceNet, PROFIBUS, PROFINET
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault, Short Circuit
Humidity95% RH or less (non-condensing)
Output VoltageMatches input voltage
Storage Temperature-25 to +70 °C

Related product manuals