3.11 L: Protection Functions
150 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
No.
(Hex.)
Name Description
Default
(Range)
L5-07
(0B2A)
Fault Reset Enable Select
Grp1
Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, the digits set
oL1, oL2, oL3, and oL4, in order.
0000 : Disabled
0001 : Enabled (///oL4)
0010 : Enabled (//oL3/)
0011 : Enabled (//oL3/oL4)
0100 : Enabled (/oL2//)
0101 : Enabled (/oL2//oL4)
0110 : Enabled (/oL2/oL3/)
0111 : Enabled (/oL2/oL3/oL4)
1000 : Enabled (oL1///)
1001 : Enabled (oL1///oL4)
1010 : Enabled (oL1//oL3/)
1011 : Enabled (oL1//oL3/oL4)
1100 : Enabled (oL1/oL2//)
1101 : Enabled (oL1/oL2//oL4)
1110 : Enabled (oL1/oL2/oL3/)
1111 : Enabled (oL1/oL2/oL3/oL4)
1111
(0000 - 1111)
L5-08
(0B2B)
Fault Reset Enable Select
Grp2
Use these 4 digits to set the Auto Restart function for Uv1, ov, oH1, and GF. From left to right, the
digits set Uv1, ov, oH1, and GF, in order.
0000 : Disabled
0001 : Enabled (///GF)
0010 : Enabled (//oH1/)
0011 : Enabled (//oH1/GF)
0100 : Enabled (/ov//)
0101 : Enabled (/ov//GF)
0110 : Enabled (/ov/oH1/)
0111 : Enabled (/ov/oH1/GF)
1000 : Enabled (Uv1///)
1001 : Enabled (Uv1///GF)
1010 : Enabled (Uv1//oH1/)
1011 : Enabled (Uv1//oH1/GF)
1100 : Enabled (Uv1/ov//)
1101 : Enabled (Uv1/ov//GF)
1110 : Enabled (Uv1/ov/oH1/)
1111 : Enabled (Uv1/ov/oH1/GF)
1111
(0000 - 1111)
L6: Torque Detection
No.
(Hex.)
Name Description
Default
(Range)
L6-01
(04A1)
Torque Detection Selection 1 Sets torque detection conditions that will trigger an overtorque or undertorque response from the
drive.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
0
(0 - 8)
L6-02
(04A2)
Torque Detection Level 1 Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
L6-03
(04A3)
Torque Detection Time 1 Sets the detection time for Overtorque/Undertorque Detection 1. 0.1 s
(0.0 - 10.0 s)

Table of Contents