Parameter List
3
3.10 H: Terminal Functions
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING 143
No.
(Hex.)
Name Description
Default
(Range)
H6-05
(0430)
RUN
Terminal RP Filter Time Sets the time constant for the pulse train input primary delay filters. 0.10 s
(0.00 - 2.00 s)
H6-06
(0431)
RUN
Terminal MP Monitor
Selection
Sets a function for pulse train monitor output terminal MP. Sets the “x-xx” part of the Ux-xx monitor. 102
(000, 031, 101, 102, 105,
116, 501, 502, 801 - 809,
821 - 825, 831 - 839, 851 -
855)
H6-07
(0432)
RUN
Terminal MP Frequency
Scaling
Sets the frequency of the pulse train output signal used when the monitor set with H6-06 [Terminal
MP Monitor Selection] is 100%.
1440 Hz
(0 - 32000 Hz)
H6-08
(043F)
Terminal RP Minimum
Frequency
Sets the minimum frequency of the pulse train signal that terminal RP can detect. 0.5 Hz
(0.1 - 1000.0 Hz)
◆ H7: Virtual MFIO Selection
No.
(Hex.)
Name Description
Default
(Range)
H7-00
(116F)
Expert
Virtual MFIO selection Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to operate the
virtual I/O function.
0 : Disabled
1 : Enabled
0
(0, 1)
H7-01
(1185)
Expert
Virtual Multi-Function Input
1
Sets the function that enters the virtual input set in H7-10 [Virtual Multi-Function Output 1].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
F
(1 - 19F)
H7-02
(1186)
Expert
Virtual Multi-Function Input
2
Sets the function that enters the virtual input set in H7-12 [Virtual Multi-Function Output 2].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
F
(1 - 19F)
H7-03
(1187)
Expert
Virtual Multi-Function Input
3
Sets the function that enters the virtual input set in H7-14 [Virtual Multi-Function Output 3].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
F
(1 - 19F)
H7-04
(1188)
Expert
Virtual Multi-Function Input
4
Sets the function that enters the virtual input set in H7-16 [Virtual Multi-Function Output 4].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
F
(1 - 19F)
H7-10
(11A4)
Expert
Virtual Multi-Function
Output 1
Sets the function for virtual digital output 1. F
(0 - 1A7)
H7-11
(11A5)
Expert
Virtual Output 1 Delay Time Sets the minimum ON time for virtual digital output 1. 0.1 s
(0.0 - 25.0 s)
H7-12
(11A6)
Expert
Virtual Multi-Function
Output 2
Sets the function for virtual digital output 2. F
(0 - 1A7)
H7-13
(11A7)
Expert
Virtual Output 2 Delay Time Sets the minimum ON time for virtual digital output 2. 0.1 s
(0.0 - 25.0 s)
H7-14
(11A8)
Expert
Virtual Multi-Function
Output 3
Sets the function for virtual digital output 3. F
(0 - 1A7)
H7-15
(11A9)
Expert
Virtual Output 3 Delay Time Sets the minimum ON time for virtual digital output 3. 0.1 s
(0.0 - 25.0 s)
H7-16
(11AA)
Expert
Virtual Multi-Function
Output 4
Sets the function for virtual digital output 4. F
(0 - 1A7)
H7-17
(11AB)
Expert
Virtual Output 4 Delay Time Sets the minimum ON time for virtual digital output 4. 0.1 s