3.10 H: Terminal Functions
144 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
No.
(Hex.)
Name Description
Default
(Range)
H7-30
(1177)
Expert
Virtual Analog Input
Selection
Sets the virtual analog input function. F
(0 - 32)
H7-31
(1178)
RUN
Expert
Virtual Analog Input Gain Sets the virtual analog input gain. 100.0%
(-999.9 - 999.9%)
H7-32
(1179)
RUN
Expert
Virtual Analog Input Bias Sets the virtual analog input bias. 0.0%
(-999.9 - 999.9%)
H7-40
(1163)
Virtual Analog Out Signal
Select
Sets the signal level of the virtual analog output.
0 : 0 to 100% (Absolute Value)
1 : -100 to 100%
2 : 0 to 100% (Lower Limit at 0)
0
(0 - 2)
H7-41
(1164)
Virtual Analog Output
Function
Sets the monitor to be output from the virtual analog output.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H7-41 = 102 to monitor U1-02 [Output
Frequency].
102
(0 - 999)
H7-42
(1165)
Virtual Analog Output
FilterTime
Sets the time constant for a primary filter of the virtual analog output. 0.00 s
(0.00 - 2.00 s)