EasyManua.ls Logo

YASKAWA GA500 - O4: Maintenance Monitors; O5: Log Function

YASKAWA GA500
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter List
3
3.13 o: Keypad-Related Settings
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING 165
o4: Maintenance Monitors
No.
(Hex.)
Name Description
Default
(Range)
o4-01
(050B)
Elapsed Operating Time
Setting
Sets the initial value of the cumulative drive operation time in 10-hour units. 0 h
(0 - 9999 h)
o4-02
(050C)
Elapsed Operating Time
Selection
Sets the condition that counts the cumulative operation time.
0 : U4-01 Shows Total Power-up Time
1 : U4-01 Shows Total RUN Time
0
(0, 1)
o4-03
(050E)
Fan Operation Time Setting Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour units. 0 h
(0 - 9999 h)
o4-05
(051D)
Capacitor Maintenance
Setting
Sets the U4-05 [CapacitorMaintenance] monitor value. 0%
(0 - 150%)
o4-07
(0523)
Softcharge Relay
Maintenance Set
Sets the U4-06 [PreChargeRelayMainte] monitor value. 0%
(0 - 150%)
o4-09
(0525)
IGBT Maintenance Setting Sets the U4-07 [IGBT Maintenance] monitor value. 0%
(0 - 150%)
o4-11
(0510)
Fault Trace/History Init (U2/
U3)
Resets the records of Monitors U2-xx [Fault Trace] and U3-xx [Fault History].
0 : Disabled
1 : Enabled
0
(0, 1)
o4-12
(0512)
kWh Monitor Initialization Resets the monitor values for U4-10 [kWh, Lower 4 Digits] and U4-11 [kWh, Upper 5 Digits].
0 : No Reset
1 : Reset
0
(0, 1)
o4-13
(0528)
RUN Command Counter @
Initialize
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [Number of Runs (Low)], and
U4-25 [Number of Runs (High)].
0 : No Reset
1 : Reset
0
(0, 1)
o4-22
(154F)
RUN
Time Format Sets the time display format. This parameter is only available when using an LCD keypad.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
1
(0 - 2)
o4-23
(1550)
RUN
Date Format Sets the date display format. This parameter is only available when using an LCD keypad.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
2
(0 - 2)
o4-24
(310F)
RUN
bAT Detection Selection Sets the operation when the drive detects bAT [Keypad Battery Low Voltage] and TiM [Keypad Time
Not Set]. This parameter is only available when you use an LCD keypad.
0 : Disable
1 : Enable (Alarm Detected)
2 : Enable (Fault Detected)
0
(0 - 2)
o5: Log Function
No.
(Hex.)
Name Description
Default
(Range)
o5-01
(1551)
RUN
Log Start/Stop Selection Sets the data log function. This parameter is only available when using an LCD keypad.
0 : OFF
1 : ON
0
(0 - 1)
o5-02
(1552)
RUN
Log Sampling Interval Sets the data log sampling cycle. This parameter is only available when using an LCD keypad. 100 ms
(100 - 60000 ms)
o5-03
(1553)
RUN
Log Monitor Data 1 Sets the data log monitor. This parameter is only available with an LCD keypad. 101
(000, 101 - 999)
o5-04
(1554)
RUN
Log Monitor Data 2 Sets the data log monitor. This parameter is only available when using an LCD keypad. 102
(000, 101 - 999)