3.10 H: Terminal Functions
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING 127
3.10 H: Terminal Functions
H1: Digital Inputs
No.
(Hex.)
Name Description
Default
(Range)
H1-01
(0438)
Terminal S1 Function
Selection
Sets the function for MFDI terminal S1.
Note:
The default setting is F when you initialize the drive for 3-Wire Initialization [A1-03 = 3330].
40
(1 - 1FF)
H1-02
(0439)
Terminal S2 Function
Selection
Sets the function for MFDI terminal S2.
Note:
The default setting is F when you initialize the drive for 3-Wire Initialization [A1-03 = 3330].
41
(1 - 1FF)
H1-03
(0400)
Terminal S3 Function
Selection
Sets the function for MFDI terminal S3. 24
(0 - 1FF)
H1-04
(0401)
Terminal S4 Function
Selection
Sets the function for MFDI terminal S4. 14
(0 - 1FF)
H1-05
(0402)
Terminal S5 Function
Selection
Sets the function for MFDI terminal S5.
Note:
The default setting is 0 when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
3
(0 - 1FF)
H1-06
(0403)
Terminal S6 Function
Selection
Sets the function for MFDI terminal S6.
Note:
The default setting is 3 when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
4
(0 - 1FF)
H1-07
(0404)
Terminal S7 Function
Selection
Sets the function for MFDI terminal S7.
Note:
The default setting is 4 when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
6
(0 - 1FF)
H1-21
(0B70)
Terminal S1 Function
Selection 2
Sets the second function for MFDI terminal S1. F
(1 - 19F)
H1-22
(0B71)
Terminal S2 Function Select
2
Sets the second function for MFDI terminal S2. F
(1 - 19F)
H1-23
(0B72)
Terminal S3 Function
Selection 2
Sets the second function for MFDI terminal S3. F
(1 - 19F)
H1-24
(0B73)
Terminal S4 Function
Selection 2
Sets the second function for MFDI terminal S4. F
(1 - 19F)
H1-25
(0B74)
Terminal S5 Function
Selection 2
Sets the second function for MFDI terminal S5. F
(1 - 19F)
H1-26
(0B75)
Terminal S6 Function
Selection 2
Sets the second function for MFDI terminal S6. F
(1 - 19F)
H1-27
(0B76)
Terminal S7 Function
Selection 2
Sets the second function for MFDI terminal S7. F
(1 - 19F)
H1-40
(0B54)
Mbus Reg 15C0h bit0 Input
Func
Sets MFDI function to set to bit 0 of the MEMOBUS register 15C0 (Hex.). F
(1 - 19F)
H1-41
(0B55)
Mbus Reg 15C0h bit1 Input
Func
Sets MFDI function to set to bit 1 of the MEMOBUS register 15C0 (Hex.). F
(1 - 19F)
H1-42
(0B56)
Mbus Reg 15C0h bit2 Input
Func
Sets MFDI function to set to bit 2 of the MEMOBUS register 15C0 (Hex.). F
(1 - 19F)
H1-xx: MFDI Setting Values
Setting Value Function Description
0 3-Wire Sequence Sets the direction of motor rotation for 3-wire sequence.
1 LOCAL/REMOTE Selection Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
ON : LOCAL
OFF : REMOTE
2 External Reference 1/2
Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
ON : b1-15 [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF : b1-01 [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]