EasyManua.ls Logo

YASKAWA GA500 - Page 126

YASKAWA GA500
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.9 F: Options
126 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
No.
(Hex.)
Name Description
Default
(Range)
F7-62
(0782)
PZD3 Write When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO output). A
value of 0, 1, or 2 will disable the PZD3 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-63
(0783)
PZD4 Write When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO output). A
value of 0, 1, or 2 will disable the PZD4 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-64
(0784)
PZD5 Write When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO output). A
value of 0, 1, or 2 will disable the PZD5 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-65
(0785)
PZD6 Write When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO output). A
value of 0, 1, or 2 will disable the PZD6 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-66
(0786)
PZD7 Write When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO output). A
value of 0, 1, or 2 will disable the PZD7 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-67
(0787)
PZD8 Write When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD8 (PPO output). A
value of 0, 1, or 2 will disable the PZD8 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-68
(0788)
PZD9 Write When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD9 (PPO output). A
value of 0, 1, or 2 will disable the PZD9 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-69
(0789)
PZD10 Write When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD10 (PPO output). A
value of 0, 1, or 2 will disable the PZD10 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-70
(078A)
PZD1 Read (Status Word) When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD1 (PPO input). PZD1
(PPO input) functions as the ZSW when F7-70 = 0.
0
F7-71
(078B)
PZD2 Read (Output
Frequency)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO input). PZD2
(PPO input) functions as the HIW when F7-71 = 0.
0
F7-72
(078C)
PZD3 Read When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO input). A
value of 0 will disable the PZD3 (PPO input) load operation from the MEMOBUS/Modbus register.
0
F7-73
(078D)
PZD4 Read When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO input). A
value of 0 will disable the PZD4 (PPO input) load operation from the MEMOBUS/Modbus register.
0
F7-74
(078E)
PZD5 Read When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO input). A
value of 0 will disable the PZD5 (PPO input) load operation from the MEMOBUS/Modbus register.
0
F7-75
(078F)
PZD6 Read When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO input). A
value of 0 will disable the PZD6 (PPO input) load operation from the MEMOBUS/Modbus register.
0
F7-76
(0790)
PZD7 Read When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO input). A
value of 0 will disable the PZD7 (PPO input) load operation from the MEMOBUS/Modbus register.
0
F7-77
(0791)
PZD8 Read When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD8 (PPO input). A
value of 0 will disable the PZD8 (PPO input) load operation from the MEMOBUS/Modbus register.
0
F7-78
(0792)
PZD9 Read When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD9 (PPO input). A
value of 0 will disable the PZD9 (PPO input) load operation from the MEMOBUS/Modbus register.
0
F7-79
(0793)
PZD10 Read When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD10 (PPO input). A
value of 0 will disable the PZD10 (PPO input) load operation from the MEMOBUS/Modbus register.
0

Table of Contents