Parameter List
3
3.5 b: Application
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING 99
No.
(Hex.)
Name Description
Default
(Setting Range)
b1-17
(01C6)
Run Command at Power Up Sets drive response when the CPU changes from de-energized to energized and there is an active Run
command. Set this parameter in applications where energizing or de-energizing the drive enables the
Run command. When the CPU stays energized during loss of power, L2-01 [Power Loss Ride
Through Select] sets operation.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
0
(0, 1)
b1-35
(1117)
Expert
Digital Input Deadband
Time
Sets the deadband time for MFDIs. 0.0 ms
(0.0 to 100.0 ms)
b2: DC Injection Braking and Short Circuit Braking
No.
(Hex.)
Name Description
Default
(Range)
b2-01
(0189)
DC Injection/Zero
SpeedThreshold
Sets the frequency to start DC Injection Braking or Short Circuit Braking near the end of a stop ramp.
Note:
This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp to Stop].
Determined by A1-02
(0.0 - 10.0 Hz)
b2-02
(018A)
DC Injection Braking
Current
Sets the DC Injection Braking current as a percentage of the drive rated current. 50%
(0 - 75%)
b2-03
(018B)
DC Inject Braking Time at
Start
Sets the DC Injection Braking Time at stop. 0.00 s
(0.00 - 10.00 s)
b2-04
(018C)
DC Inject Braking Time at
Stop
Sets the DC Injection Braking Time at stop. Determined by A1-02
(0.00 - 10.00 s)
b2-08
(0190)
Magnetic Flux
Compensation Value
Sets how much current the drive injects when DC Injection Braking at Start starts (Initial Excitation)
as a percentage of E2-03 [Motor No-Load Current].
0%
(0 - 1000%)
b2-12
(01BA)
Short Circuit Brake Time @
Start
Sets the Short Circuit Braking time at start. 0.00 s
(0.00 - 25.50 s)
b2-13
(01BB)
Short Circuit Brake Time @
Stop
Sets the Short Circuit Braking time at stop. A1-02 = 8: 0.00 s
Other than A1-02 = 8: 0.50 s
(0.00 - 25.50 s)
b2-18
(0177)
Short Circuit Braking
Current
Sets the Short Circuit Braking Current as a percentage of the motor rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor rated current.
A1-02 = 5, 6 [OLV/PM, AOLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
100.0%
(0.0 - 200.0%)
b3: Speed Search
No.
(Hex.)
Name Description
Default
(Range)
b3-01
(0191)
Speed Search at Start
Selection
Sets the Speed Search at Start function so the drive will do Speed Search with each Run command.
0 : Disable
1 : Enabled
Determined by A1-02
(0, 1)
b3-02
(0192)
SpeedSearch Deactivation
Current
Sets the current level that stops Speed Search as a percentage of the drive rated output current.
Usually it is not necessary to change this setting.
Determined by A1-02
(0 - 200%)
b3-03
(0193)
Speed Search Deceleration
Time
Sets the deceleration time during Speed Search operation. Set the length of time to decelerate from
the maximum output frequency to the minimum output frequency.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this parameter takes effect only in
Expert Mode.
2.0 s
(0.1 - 10.0 s)
b3-04
(0194)
V/f Gain during Speed
Search
Sets the ratio used to reduce the V/f during searches to reduce the output current during speed
searches.
Determined by o2-04
(10 - 100)
b3-05
(0195)
Speed Search Delay Time Sets the Speed Search delay time to activate a magnetic contactor installed between the drive and
motor.
0.2 s
(0.0 - 100.0 s)
b3-06
(0196)
Expert
Speed Estimation Current
Level 1
Sets the level of current that flows to the motor during Speed Estimation Speed Search as a
coefficient of the motor rated current. Usually it is not necessary to change this setting.
Determined by o2-04
(0.0 - 2.0)