Parameter List
3
3.10 H: Terminal Functions
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING 131
Setting Value Function Description
9F DWEZ Disable Sets operation of the DriveWorksEZ program saved in the drive.
ON : Disabled
OFF : Enabled
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Enabled/Disabled wDigital Input] to use this function.
101 to 19F
Inverse Input of 1 to 9F Sets the function of the selected MFDI to operate inversely. To select the function, enter “1xx”, where the “xx” is the function setting
value.
Note:
You cannot use inverse input for all functions. Refer to the Technical Reference or Programming Manual for details.
◆ H2: Digital Outputs
No.
(Hex.)
Name Description
Default
(Range)
H2-01
(040B)
Term MA/MB-MC Function
Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through
mode.
E
(0 - 1FF)
H2-02
(040C)
Term P1-C1 Function
Selection
Sets the function for MFDO terminal P1-C1.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through
mode.
0
(0 - 1FF)
H2-03
(040D)
Term P2-C2 Function
Selection
Sets the function for MFDO terminal P2-C2.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through
mode.
2
(0 - 1FF)
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
0
(0 - 4)
H2-07
(0B3A)
Modbus Register 1 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal. 0001
(0001 - 1FFF)
H2-08
(0B3B)
Modbus Register 1 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal. 0000
(0000 - FFFF)
H2-09
(0B3C)
Modbus Register 2 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal. 0001
(0001 - 1FFF)
H2-10
(0B3D)
Modbus Register 2 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal. 0000
(0000 - FFFF)
H2-20
(1540)
Comparator 1 Monitor
Selection
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For example, set
H2-20 = 102 to monitor U1-02 [Output Frequency].
102
(000 - 999)
H2-21
(1541)
Comparator 1 Lower Limit Sets the lower limit detection level for comparator 1 when the full scale analog output for the monitor
selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
H2-22
(1542)
Comparator 1 Upper Limit Sets the upper limit detection level for comparator 1 when the full scale analog output for the monitor
selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
H2-23
(1543)
Comparator 1 Hysteresis Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the
monitor selected in H2-20 [Comparator 1 Monitor Selection].
0.0%
(0.0 - 10.0%)
H2-24
(1544)
Comparator 1 On-Delay
Time
Sets the on-delay time for comparator 1. 0.0 s
(0.0 - 600.0 s)
H2-25
(1545)
Comparator 1 Off-Delay
Time
Sets the off-delay time for comparator 1. 0.0 s
(0.0 - 600.0 s)
H2-26
(1546)
Comparator 2 Monitor
Selection
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [Monitor]. For example, set
H2-26 = 103 to monitor U1-03 [Output Current].
103
(000 - 999)
H2-27
(1547)
Comparator 2 Lower Limit Sets the lower limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 300.0%)
H2-28
(1548)
Comparator 2 Upper Limit Sets the upper limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 300.0%)