◆ H3: Analog Inputs
No.
(Hex.)
Name Description
Default
(Range)
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
4 : -10 to +10V (Bipolar Reference)
0
(0, 4)
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1. 0
(0 - 32)
H3-03
(0411)
RUN
Terminal A1 Gain Setting Sets the gain of the analog signal input to MFAI terminal A1. 100.0%
(-999.9 - +999.9%)
H3-04
(0412)
RUN
Terminal A1 Bias Setting Sets the bias of the analog signal input to MFAI terminal A1. 0.0%
(-999.9 - +999.9%)
H3-09
(0417)
Terminal A2 Signal Level
Select
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
4 : -10 to +10V (Bipolar Reference)
2
(0, 2 - 4)
H3-10
(0418)
Terminal A2 Function
Selection
Sets the function for MFAI terminal A2. 0
(0 - 32)
H3-11
(0419)
RUN
Terminal A2 Gain Setting Sets the gain of the analog signal input to MFAI terminal A2. 100.0%
(-999.9 - +999.9%)
H3-12
(041A)
RUN
Terminal A2 Bias Setting Sets the bias of the analog signal input to MFAI terminal A2. 0.0%
(-999.9 - +999.9%)
H3-13
(041B)
Analog Input FilterTime
Constant
Sets the time constant for primary delay filters on MFAI terminals. 0.03 s
(0.00 - 2.00 s)
H3-14
(041C)
Analog Input Terminal
Enable Sel
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog Terminal
Enable Selection] is ON.
1 : Terminal A1 only
2 : Terminal A2 only
7 : Terminals A1 and A2
7
(1, 2, 7)
H3-16
(02F0)
Terminal A1 Offset Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to change this
setting.
0
(-500 - +500)
H3-17
(02F1)
Terminal A2 Offset Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to change this
setting.
0
(-500 - +500)
H3-40
(0B5C)
Mbus Reg 15C1h Input
Function
Sets the MEMOBUS AI1 function. F
(4 - 2F)
H3-41
(0B5F)
Mbus Reg 15C2h Input
Function
Sets the MEMOBUS AI2 function. F
(4 - 2F)
H3-42
(0B62)
Mbus Reg 15C3h Input
Function
Sets the MEMOBUS AI3 function. F
(4 - 2F)
H3-43
(117F)
Mbus Reg Inputs FilterTime
Const
Sets the time constant to apply a primary delay filter to the MEMOBUS analog input register values. 0.00 s
(0.00 - 2.00 s)
■ H3-xx: MFAI Setting Values
Setting Value Function Description
0 Frequency Reference The input value from the MFAI terminal set with this function becomes the master frequency reference.
1 Frequency Gain The drive multiplies the analog frequency reference with the input value from the MFAI set with this function.
2 Auxiliary Frequency
Reference 1
Sets Reference 2 through multi-step speed reference to enable the command reference (Auxiliary Frequency Reference 1) from the
analog input terminal set here. This value is a percentage where the Maximum Output Frequency setting is a setting value of 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]