3.8 E: Motor Parameters
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING 117
No.
(Hex.)
Name Description
Default
(Range)
E3-08
(031E)
Motor 2 Mid Point A Voltage Sets a middle output voltage for the motor 2 V/f pattern. Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
E3-09
(031F)
Motor 2 Minimum Output
Frequency
Sets the minimum output frequency for the motor 2 V/f pattern. Determined by E3-01
(0.0 - E3-04)
E3-10
(0320)
Motor 2 Minimum Output
Voltage
Sets the minimum output voltage for the motor 2 V/f pattern. Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
E3-11
(0345)
Expert
Motor 2 Mid Point B
Frequency
Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust the V/f
pattern for the constant output range. Usually it is not necessary to change this parameter.
0.0 Hz
(0.0 - E3-04)
E3-12
(0346)
Expert
Motor 2 Mid Point B Voltage Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern
for the constant output range. Usually it is not necessary to change this parameter.
0.0 V
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
E3-13
(0347)
Expert
Motor 2 Base Voltage Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the
constant output range. Usually it is not necessary to change this parameter.
0.0 V
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
E4: Motor 2 Parameters
No.
(Hex.)
Name Description
Default
(Range)
E4-01
(0321)
Motor 2 Rated Current Sets the motor rated current for motor 2 in amps. Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
E4-02
(0322)
Motor 2 Rated Slip Sets the motor rated slip for motor 2. Determined by o2-04, C6-01
(0.000 - 20.000 Hz)
E4-03
(0323)
Motor 2 Rated No-Load
Current
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the no-load
voltage.
Determined by o2-04, C6-01
(0 to E4-01)
E4-04
(0324)
Motor 2 Motor Poles Sets the number of poles for motor 2. 4
(2 - 120)
E4-05
(0325)
Motor 2 Line-to-Line
Resistance
Sets the line-to-line resistance for the motor 2 stator windings. Determined by o2-04, C6-01
(0.000 - 65.000 Ω)
E4-06
(0326)
Motor 2 Leakage Inductance Sets the voltage drop from motor 2 leakage inductance as a percentage of Motor Rated Voltage when
motor 2 operates at the rated frequency and rated current.
Determined by o2-04, C6-01
(0.0 - 60.0%)
E4-07
(0343)
Motor 2 Saturation
Coefficient 1
Sets the motor 2 iron-core saturation coefficient at 50% of the magnetic flux. 0.50
(0.00 - 0.50)
E4-08
(0344)
Motor 2 Saturation
Coefficient 2
Sets the motor 2 iron-core saturation coefficient at 75% of the magnetic flux. 0.75
(E4-07 - 0.75)
E4-09
(033F)
Expert
Motor 2 Mechanical Loss Sets the mechanical loss of motor 2. It is set as a percentage of E4-11 [Motor 2 Rated Power].
Usually it is not necessary to change this setting.
0.0%
(0.0 - 10.0%)
E4-10
(0340)
Motor 2 Iron Loss Sets the motor iron loss for motor 2. Determined by o2-04, C6-01
(0 - 65535 W)
E4-11
(0327)
Motor 2 Rated Power Sets the motor rated power in the units from o1-58 [Motor Power Unit Selection]. Determined by o2-04, C6-01
(0.00 - 650.00 HP)
E5: PM Motor Settings
No.
(Hex.)
Name Description
Default
(Range)
E5-01
(0329)
PM Motor Code Selection Sets the motor code for Yaskawa PM motors. The drive uses the motor code to automatically set
some parameters to their correct settings.
FFFF
(0000 - FFFF)
E5-02
(032A)
PM Motor Rated Power Sets the PM motor rated output in the units from o1-58 [Motor Power Unit Selection]. Determined by o2-04, C6-01
(0.10 - 30.00 kW)