Parameter List
3
3.6 C: Tuning
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING 107
3.6 C: Tuning
C1: Accel & Decel Time
No.
(Hex.)
Name Description
Default
(Range)
C1-01
(0200)
RUN
Acceleration Time 1 Sets the length of time to accelerate from zero to maximum output frequency. 10.0 s
(0.0 - 6000.0 s)
C1-02
(0201)
RUN
Deceleration Time 1 Sets the length of time to decelerate from maximum output frequency to zero. 10.0 s
(0.0 - 6000.0 s)
C1-03
(0202)
RUN
Acceleration Time 2 Sets the length of time to accelerate from zero to maximum output frequency. 10.0 s
(0.0 - 6000.0 s)
C1-04
(0203)
RUN
Deceleration Time 2 Sets the length of time to decelerate from maximum output frequency to zero. 10.0 s
(0.0 - 6000.0 s)
C1-05
(0204)
RUN
Acceleration Time 3 Sets the length of time to accelerate from zero to maximum output frequency. 10.0 s
(0.0 - 6000.0 s)
C1-06
(0205)
RUN
Deceleration Time 3 Sets the length of time to decelerate from maximum output frequency to zero. 10.0 s
(0.0 - 6000.0 s)
C1-07
(0206)
RUN
Acceleration Time 4 Sets the length of time to accelerate from zero to maximum output frequency. 10.0 s
(0.0 - 6000.0 s)
C1-08
(0207)
RUN
Deceleration Time 4 Sets the length of time to decelerate from maximum output frequency to zero. 10.0 s
(0.0 - 6000.0 s)
C1-09
(0208)
RUN
Fast Stop Time Sets the length of time that the drive will decelerate to zero for a Fast Stop.
Note:
Decelerating too quickly can cause an ov [Overvoltage] fault that shuts off the drive while the
motor to coasts to a stop. Set a Fast Stop time in C1-09 that prevents motor coasting and makes
sure that the motor stops quickly and safely.
When L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 1] and you do
KEB Auto-Tuning, the drive will automatically set C1-09. If you must not change the Fast Stop
time, do not do KEB Tuning.
10.0 s
(0.0 - 6000.0 s)
C1-10
(0209)
Accel/Decel Time Setting
Units
Sets the setting units for C1-01 to C1-08 [Accel/Decel Times 1 to 4], C1-09 [Fast Stop Time], L2-06
[Kinetic Energy Backup Decel Time], and L2-07 [Kinetic Energy Backup Accel Time].
0 : 0.01 s (0.00 to 600.00 s)
1 : 0.1 s (0.0 to 6000.0 s)
1
(0, 1)
C1-11
(020A)
Accel/Decel Time Switching
Frequency
Sets the frequency at which the drive will automatically change acceleration and deceleration times. Determined by A1-02
(0.0 - 590.0 Hz)
C1-14
(0264)
RUN
Accel/Decel Rate Frequency Sets the base frequency used to calculate acceleration and deceleration rates. 0.0 Hz
(0.0 - 590.0 Hz)
C2: S-Curve Characteristics
No.
(Hex.)
Name Description
Default
(Range)
C2-01
(020B)
S-Curve Time @ Start of
Accel
Sets the S-curve acceleration time at start. Determined by A1-02
(0.00 - 10.00 s)
C2-02
(020C)
S-Curve Time @ End of
Accel
Sets the S-curve acceleration time at completion. 0.20 s
(0.00 - 10.00 s)
C2-03
(020D)
S-Curve Time @ Start of
Decel
Sets the S-curve deceleration time at start. 0.20 s
(0.00 - 10.00 s)
C2-04
(020E)
S-Curve Time @ End of
Decel
Sets the S-curve deceleration time at completion. 0.00 s
(0.00 - 10.00 s)