3.5 b: Application
102 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
b5: PID control
No.
(Hex.)
Name Description
Default
(Range)
b5-01
(01A5)
PID Mode Setting Sets the type of PID control.
0 : Disabled
1 : Standard
2 : Standard (D on feedback)
3 : Fref + PID Trim
4 : Fref + PID Trim (D on feedback)
5 : Same as 7series & prior, b5-01=1
6 : Same as 7series & prior, b5-01=2
7 : Same as 7series & prior, b5-01=3
8 : Same as 7series & prior, b5-01=4
Note:
Use settings 5 to 8 instead of settings 1 to 4 when the drive is a replacement for Varispeed F7.
0
(0 - 8)
b5-02
(01A6)
RUN
Proportional Gain (P) Sets the proportional gain (P) that is applied to PID input. 1.00
(0.00 - 25.00)
b5-03
(01A7)
RUN
Integral Time (I) Sets the integral time (I) that is applied to PID input. 1.0 s
(0.0 - 360.0 s)
b5-04
(01A8)
RUN
Integral Limit Sets the upper limit for integral control (I) as a percentage of the Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
100.0%
(0.0 - 100.0%)
b5-05
(01A9)
RUN
Derivative Time (D) Sets the derivative time (D) for PID control. This parameter adjusts system responsiveness. 0.00 s
(0.00 - 10.00 s)
b5-06
(01AA)
RUN
PID Output Limit Sets the maximum possible output from the PID controller as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
100.0%
(0.0 - 100.0%)
b5-07
(01AB)
RUN
PID Offset Adjustment Sets the offset for the PID control output as a percentage of the Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
A1-02 8 [EZOLV]: E1-04 [Maximum Output Frequency]
A1-02 = 8: E9-02 [Maximum Speed]
0.0%
(-100.0 - +100.0%)
b5-08
(01AC)
RUN
Expert
PID Primary Delay Time
Constant
Sets the primary delay time constant for the PID control output. Usually it is not necessary to change
this setting.
0.00 s
(0.00 - 10.00 s)
b5-09
(01AD)
PID Output Level Selection Sets the polarity of the PID output.
0 : Normal Output (Direct Acting)
1 : Reverse Output (Reverse Acting)
0
(0, 1)
b5-10
(01AE)
RUN
PID Output Gain Setting Sets the amount of gain to apply to the PID output. 1.00
(0.00 - 25.00)
b5-11
(01AF)
PID Output Reverse
Selection
Sets the function that enables and disables reverse motor rotation for negative PID control output.
0 : Lower Limit is Zero
1 : Negative Output Accepted
0
(0, 1)