3.10 H: Terminal Functions
132 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
No.
(Hex.)
Name Description
Default
(Range)
H2-29
(1549)
Comparator 2 Hysteresis Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for the
monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 10.0%)
H2-30
(154A)
Comparator 2 On-Delay
Time
Sets the on-delay time for comparator 2. 0.0 s
(0.0 - 600.0 s)
H2-31
(154B)
Comparator 2 Off-Delay
Time
Sets the off-delay time for comparator 2. 0.0 s
(0.0 - 600.0 s)
H2-32
(159A)
Comparator 1 Filter Time Sets the time constant that is applied to the primary delay filter used for the analog output of the
monitor selected with H2-20 [Comparator 1 Monitor Selection].
0.0s
(0.0 - 10.0 s)
H2-33
(159B)
Comparator1 Protection
Selection
Sets drive operation when it detects CP1 [Comparator1 Limit Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Digital Output Only
4
(0 - 4)
H2-34
(159C)
Comparator 2 Filter Time Sets the time constant that is applied to the primary delay filter used for the analog output of the
monitor selected with H2-26 [Comparator 2 Monitor Selection].
0.0s
(0.0 - 10.0 s)
H2-35
(159D)
Comparator2 Protection
Selection
Sets drive operation when it detects CP2 [Comparator2 Limit Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Digital Output Only
4
(0 - 4)
H2-36
(159E)
Comparator 1 Ineffective
Time
Sets the length of time that CP1 [Comparator1 Limit Fault] is disabled. 0.0 s
(0.0 - 1000.0 s)
H2-37
(159F)
Comparator 2 Ineffective
Time
Sets the length of time that CP2 [Comparator2 Limit Fault] is disabled. 0.0 s
(0.0 - 1000.0 s)
H2-40
(0B58)
Mbus Reg 15E0h bit0
Output Func
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.). F
(0 - 1FF)
H2-41
(0B59)
Mbus Reg 15E0h bit1
Output Func
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.). F
(0 - 1FF)
H2-42
(0B5A)
Mbus Reg 15E0h bit2
Output Func
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.). F
(0 - 1FF)
H2-60
(1B46)
Expert
Term MA,MB,MC
Secondary Function
Sets the second function for terminal MA/MB-MC. Outputs the logical calculation results of the
terminals set to functions by H2-01 [Term MA,MB,MC Function Selection].
F
(0 - FF)
H2-61
(1B47)
Expert
Term MA,MB,MC Logical
Operation
Sets the logical operation for the functions set in H2-01 [Term MA,MB,MC Function Selection] and
H2-60 [Term MA,MB,MC Secondary Function].
0
(0 - 8)
H2-62
(1B48)
Expert
Term MA,MB,MC
Minimum ON Time
Sets the minimum ON time that the drive uses to output the logical calculation results from terminal
MA/MB-MC.
0.1 s
(0.0 - 25.0 s)
H2-63
(1B49)
Expert
Terminal P1 Secondary
Function
Sets the second function for terminal P1-C1. Outputs the logical calculation results of the terminals
set to functions by H2-02 [Term P1 Function Selection].
F
(0 - FF)
H2-64
(1B4A)
Expert
Terminal P1 Logical
Operation
Sets the logical operation for the functions set in H2-02 [Term P1 Function Selection] and H2-63
[Terminal P1 Secondary Function].
0
(0 - 8)
H2-65
(1B4B)
Expert
Terminal P1 Minimum ON
Time
Sets the minimum ON time used to output the logical calculation results from terminal P1-C1. 0.1 s
(0.0 - 25.0 s)
H2-66
(1B4C)
Expert
Terminal P2 Secondary
Function
Sets the second function for terminal P2-C2. Outputs the logical calculation results of the terminals
assigned to functions by H2-03 [Term P2 Function Selection].
F
(0 - FF)