2.6 Parameter Setting Errors
74 YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Code Name Causes Possible Solutions
oPE33 Digital Output Selection Error
These two parameters are set at the same time:
H2-60 F [Term MA,MB,MC Secondary Function
Not Used]
H2-01 = 1xx [Term MA,MB,MC Function
Selection = Inverse output of xx]
These two parameters are set at the same time:
H2-63 F [Terminal P1 Secondary Function
Not Used]
H2-02 = 1xx [Term P1 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
H2-66 F [Terminal P2 Secondary Function
Not Used]
H2-03 = 1xx [Term P2 Function Selection =
Inverse output of xx]
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
If you use the function to output logical calculation results (H2-
60, H2-63, H2-66 F), you cannot set H2-01 to H2-03 = 1xx.
These parameter pairs are set incorrectly:
H2-21 [Comparator 1 Lower Limit] > H2-22
[Comparator 1 Upper Limit]
H2-27 [Comparator 2 Lower Limit] > H2-28
[Comparator 2 Upper Limit]
Set parameters H2-21 H2-22.
Set parameters H2-27 H2-28.